2007-08-14 07:56:38BUILDING PLAN REVIEW
 PERMIT: 07050064
 ADD: 529 S.FLAGLER DR. #2307
 CONT: ROBBINS CONSULTING
 TEL: (561)744-5788
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE TWO COMPLETE SETS OF DRAWINGS SHOWING THE
 EXISTING AND PROPOSED LAYOUT OF THE PROJECT. INDICATE
 CLEARLY WHICH WALL WILL BE REMOVED AND WHERE THE NEW
 WALLS WILL BE CONSTRUCTED. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES,RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 106.1.1. THE PLANS SHALL INCLUDE A LEGEND SHOWING THE
 EXISTING WALLS AND THE NEW WALLS. ALSO A DETAIL OF THE
 NEW WALLS SHALL BE INDICATED ON THE PLANS.
  
 3)OK
  
 4)OK
  
 5)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 NEW****
 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 "PARTIALLY ADDRESSED". HOWEVER, THE LEVEL OF ALTERATION
 INDICATED ON THE DRAWINGS IS INCORRECT. THE DRAWINGS
 INDICATE NEW WALLS AND DOORS. LEVEL 2 ALTERATION
 INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR
 ELIMATION OF ANY DOOR OR WINDOW, THE EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT. FBC EXISTING SEC. 304.1
  
 "NO RESPONSE".
 FBC. 1207.3FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC OR
 SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492. PROVIDE
 INFORMATION MEETING THIS REQUIREMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected].