Plan Review Notes
Plan Review Notes For Permit 07050064
Permit Number 07050064
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-06 19:02:44 
 ** UNSAT 2ND REVIEW **
  
 *** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED FULLY.
 *** PLEASE ALSO SEE NEW COMMENTS BASED ON THE FACT THAT
 PLANS ARE NOW BEING SUBMITTED FOR THE FIRST REVIEW.
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE NFPA-72 AND REQUIRED NEW OR
 EXISTING SMOKE ALARMS OR DETECTORS DEPENDING ON THE
 SYSTEM BEING INSTALLED. PLEASE SEE FBC R313 AS THE
 SMOKE DEVICES IS REQUIRED TO BE BROUGHT UP TO THE
 CURRENT CODE. PLEASE SEE NFPA-72 11.5.1.1.1 AND 11.8.3
 FOR LOCATION, TYPE REQUIREMENTS. INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS, INTERCONNECTED ETC.
 THIS WAS REQUIRED ON PREVIOUS REVIEW:
 PLEASE SEE THE FOLLOWING COMMENT;
  
 3) NOTE: PLEASE KNOW IF THESE DEVICES ARE NEW BEING
 ADDED TO THE EXISTING BEDROOMS/SLEEPING ROOMS, THEN
 PLEASE SEE 210.12 OF THE NEC FOR REQUIRED AFCI
 PROTECTION.
  
 4) NOTE: PLEASE SHOW AND INDICATE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR NEW AND EXISTING LOADS.
 THIS WAS REQUESTED ON PREVIOUS REVIEW AND THIS WAS NOT
 DONE.
 PLEASE SEE 408.4, 310.16, 24.4 ETC.
 PLEASE COMPLETE THE MINIMUM REQUIRED DEDICATED CIRCUITS
 PER NEC.
  
 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER
 220.83.
 PLEASE SEE MISSING SMALL APPLIANCE CIRCUITS ETC.
 220.52
 PLEASE SEE MISSING REQUIRED DEDICATED BATH CIRCUITS PER
 210.11C3
 PLEASE SEE OTHER DEDICATED CIRCUITS AS SHOWN ON PLANS
 WHICH NEED TO BE ON PANEL SCHEDULE AS WELL AS IN LOAD
 CALCULATIONS.220.54, 220.55 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE 210.4B FOR POSSIBLE
 DISHWASHER/DISPOSAL TO SAME YOKE.
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE ELECTRICAL
 PANEL PER 110.26, 408.7, 240.24.
 LOCATION CAN NOT BE VERIFIED AT THIS TIME.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II