| 2007-05-09 15:13:15 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR SCOPE OF |
| | WORK INCLUDING ALL TRADES. |
| | FBC106.3.5.4, 106.1.2 |
| | PLEASE SEE THE PLANS SHALL BE DONE BY A MINIMUM OF AN |
| | ARCHITECT. PERFS 481.229 |
| | PLEASE BE SURE ALL CODES ADOPTED AS OF DECEMBER 8TH, |
| | 2006 ARE STATED ON PLANS. |
| | PLEASE SEE ELECTRICAL SCOPE OF WORK IS UNDER THE 2005 |
| | NFPA-70 AND 2002 NFPA-72. |
| | PLEASE SEE THE 2004 FBC W/2006 REVISION. |
| | PLEASE SHOW AND INCLUDING ALL MINIMUM CIRCUITING ALONG |
| | WITH COMPLETE PANEL SCHEDULE AND LOAD CALCULATIONS PER |
| | 2005 NEC. |
| | 408.4, 310.16, 240.4, 210.52, 210.11, 220 ETC. |
| | |
| | NO COMPLETE PLANS OR PLANS SUBMITTED FOR REVIEW. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |