| 2008-05-30 10:18:50 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE REVISIONS NOW COMING IN FOR |
| | REVIEW DO NOT COORDINATE WITH RECORD PLANS ON FILE. |
| | THE LAST REVISION ON FILE WITH THE CITY IS REVISION #6, |
| | NOW WE HAVE REVISION #16 COMING IN WITH OUT SHOWING |
| | OTHER REVISIONS BETWEEN THE TWO. |
| | PLEASE SEE SOME REVISIONS AND CLOUDS ON PLANS, HOWEVER |
| | BASED EVEN ON THE #6 REVISION ALREADY ON FILE THERE IS |
| | NO CHANGES FROM PREVIOUS PLANS. |
| | PLEASE SEE FILE/STORAGE ROOM FOR ONE EXAMPLE. |
| | PLEASE SEE OTHER WHICH INDICATES WALL TO BE REMOVED |
| | HOWEVER ALL PREVIOUS PLANS NEVER CONTAINED A WALL. THIS |
| | IS THE WALL OUTSIDE FLOOR ELECTRICAL ROOM. |
| | |
| | ** PLEASE COORDINATE ALL. |
| | |
| | 2) NOTE: THE LETTER SUBMITTED ALONG WITH THE PLANS NOW |
| | REQUEST DE-RATINGS FOR HEATER UNITS WHICH CAN NOT BE |
| | FOUND IN THE CODE. THE LETTER MENTIONS PROGRAMMING OF |
| | SYSTEM AND HOW THE SYSTEM *SHOULD* WORK SO THAT LOADS |
| | ARE NOT AT MINIMUM PER NEC. PLEASE KNOW THIS OFFICE IS |
| | NOT AWARE OF ANY LOCATION IN THE CODE FOR DE-RATING DUE |
| | TO PROGRAMMING OF A SYSTEM OR HOW ONE SYSTEM *SHOULD* |
| | OPERATE. 220, 220.51, ETC |
| | FBC 106.3.5.1.2 |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |