| Date |
Text |
| 2007-11-03 12:36:21 | ** NOTE ADDED 11/3/07. |
| | |
| | 1) NOTE: NEED TO VERIFY ON LIGHTING CALCULATIONS SHEET |
| | THE ADDITIONAL WATTAGE BEING SHOWN WHICH EXCEEDS THE |
| | TABLE ALLOWANCES. IF THERE IS ADDITIONAL WATTAGE IS |
| | BEING FIGURED FROM THE CODE PLEASE EXPLAIN AND |
| | INDICATE ON TABLE WHICH LOCATIONS/ROOMS ARE USING THE |
| | ADDITIONAL WATTAGE WHICH MAY BE PERMITTED UNDER |
| | 13-415.2.B.2. |
| | ONLY ROOMS WHICH CONTAIN THE LIGHTING FOR DECORATIVE |
| | PURPOSES ARE PERMITTED TO USE THE ADDITIONAL WATTAGE OF |
| | 1.0 PER SQ FT. IF ROOM ONLY CONTAINS GENERAL LIGHTING, |
| | THEN THE TABLE AS SPECIFIED IN13-415.2.B MAY ONLY BE |
| | USED. |
| 2007-11-02 09:31:56 | |
| | ** DENIED 3RD REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE COMMENT #1 FROM PREVIOUS REVIEW |
| | WHICH SPECIFICALLY GAVE THE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 FOR ALL INFORMATION REQUIRED ON TITLE |
| | BLOCKS. PLEASE SEE ONCE MORE THESE WERE NOT COMPLETED. |
| | PLEASE SEE THESE ARE STILL MISSING THE REQUIRED PRINTED |
| | NAME OF THE ENGINEER ON TITLE BLOCKS. |
| | FS 471.025 |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHT FIXTURE SCHEDULE ON |
| | A00.31 DOES NOTE CORRELATE WITH THE LIGHTING FIXTURES |
| | ON E-0.2. |
| | |
| | 3) NOTE: PLEASE SEE 13-415.1.ABC.1.3 AND THE REQUIRED |
| | ADDITIONAL CONTROL FOR ACCENT/TASK LIGHTING. PLEASE SEE |
| | THE RESPONSE MENTIONS THE FIXTURE *K* WILL HAVE A |
| | ROCKER SWITCH. DOES THIS HAVE AN AUTOMATIC WAY OF |
| | TURNING OFF? IN SOME LOCATIONS THESE CONTAIN A |
| | DESIGNATION LETTER IN WHICH THE ROOM OCCUPANCY SENSOR |
| | OR CONTROL DEVICE IS CLEAR HOWEVER THERE ARE LOCATIONS |
| | WHICH NO DESIGNATIONS OR CONTROLS COULD BE LOCATED. |
| | PLEASE SEE THE *K* FIXTURES IN BETWEEN WHAT APPEARS TO |
| | BECAF? 11D03 ANDCOPY 11E03. THESE CONTAIN AN *82* |
| | HOWEVER NO OTHER CONTROL DESIGNATION WAS LOCATED. |
| | PLEASE SEE THE FOLLOWING NOTE WITH RESPECT TO |
| | CIRCUITING AS THIS AFFECTS SOME *K* FIXTURES AS WELL. |
| | |
| | 4) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS AND |
| | PANEL SCHEDULES. THIS AFFECT THE LIGHTING CONTROLS AS |
| | WELL. FOR SOME EXAMPLES PLEASE SEE THE FOLLOWING. |
| | PLEASE SEE ROOM 11H06 WHICH CONTAINS *K* FIXTURES, |
| | THESE ARE SHOWN CIRCUITED IN TWO LOCATIONS AND BOTH |
| | SHOW THE SAME CIRCUIT P2102-28. THIS CIRCUIT AS SHOWN |
| | IN THE PANEL P2102 IS FOR ROOM 11D03 WATER DISPENSER. |
| | PLEASE SEE ROOM/AREA RIGHT OUTSIDE OF COPY ROOM 11E03 |
| | WHICH CONTAINS CIRCUITING P211-82. NO PANEL P211 COULD |
| | BE LOCATED ON PLANS.ONLY TWO PANEL SCHEDULES WHICH |
| | CONTAIN SUB-SECTIONS WHICH DO CONTAIN A CIRCUIT/SPACE |
| | 82 ARE SHOWN AS SPARES/SPACE WITH NOT INDICATION OF |
| | LIGHTING. |
| | PLEASE SEE THE OTHER FIXTURES IN THIS AREA WHICH ARE |
| | ALSO LABELED WITH THE SAME 82. |
| | ** AS MENTION ON PREVIOUS REVIEW AND IN MEETING HELD |
| | THESE ARE SOME EXAMPLES. PLEASE GO OVER ALL CIRCUITING |
| | AND COORDINATE WITH PANEL SCHEDULES, CONTROLS ETC. |
| | 408.4, 240.4, 310.16. |
| | FBC 13-415.1.ABC.1.1, .1.2, .1.3 (AS NOTED ABOVE) FBC |
| | 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE FP SHEETS WHICH ARE MISSING THE |
| | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER. THE SHEET |
| | ATTACHED TO THESE SHEETS MAY NOT BE USED TO TAKE PLACE |
| | OF THE REQUIRED INFORMATION ON TITLE BLOCKS OF SIGNED |
| | AND SEALED PLANS. THIS INFORMATION MAY BE PRINTED ON |
| | SHEETS AND IS BEING GIVEN AS INFORMATION AT THIS TIME. |
| | THIS COMMENT IS NOT FOR AHA. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |