Plan Review Notes
Plan Review Notes For Permit 07050059
Permit Number 07050059
Review Stop E
Sequence Number 3
Notes
Date Text
2007-11-03 12:36:21** NOTE ADDED 11/3/07.
  
 1) NOTE: NEED TO VERIFY ON LIGHTING CALCULATIONS SHEET
 THE ADDITIONAL WATTAGE BEING SHOWN WHICH EXCEEDS THE
 TABLE ALLOWANCES. IF THERE IS ADDITIONAL WATTAGE IS
 BEING FIGURED FROM THE CODE PLEASE EXPLAIN AND
 INDICATE ON TABLE WHICH LOCATIONS/ROOMS ARE USING THE
 ADDITIONAL WATTAGE WHICH MAY BE PERMITTED UNDER
 13-415.2.B.2.
 ONLY ROOMS WHICH CONTAIN THE LIGHTING FOR DECORATIVE
 PURPOSES ARE PERMITTED TO USE THE ADDITIONAL WATTAGE OF
 1.0 PER SQ FT. IF ROOM ONLY CONTAINS GENERAL LIGHTING,
 THEN THE TABLE AS SPECIFIED IN13-415.2.B MAY ONLY BE
 USED.
2007-11-02 09:31:56 
 ** DENIED 3RD REVIEW **
  
  
 1) NOTE: PLEASE SEE COMMENT #1 FROM PREVIOUS REVIEW
 WHICH SPECIFICALLY GAVE THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 FOR ALL INFORMATION REQUIRED ON TITLE
 BLOCKS. PLEASE SEE ONCE MORE THESE WERE NOT COMPLETED.
 PLEASE SEE THESE ARE STILL MISSING THE REQUIRED PRINTED
 NAME OF THE ENGINEER ON TITLE BLOCKS.
 FS 471.025
  
 2) NOTE: PLEASE SEE THE LIGHT FIXTURE SCHEDULE ON
 A00.31 DOES NOTE CORRELATE WITH THE LIGHTING FIXTURES
 ON E-0.2.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.3 AND THE REQUIRED
 ADDITIONAL CONTROL FOR ACCENT/TASK LIGHTING. PLEASE SEE
 THE RESPONSE MENTIONS THE FIXTURE *K* WILL HAVE A
 ROCKER SWITCH. DOES THIS HAVE AN AUTOMATIC WAY OF
 TURNING OFF? IN SOME LOCATIONS THESE CONTAIN A
 DESIGNATION LETTER IN WHICH THE ROOM OCCUPANCY SENSOR
 OR CONTROL DEVICE IS CLEAR HOWEVER THERE ARE LOCATIONS
 WHICH NO DESIGNATIONS OR CONTROLS COULD BE LOCATED.
 PLEASE SEE THE *K* FIXTURES IN BETWEEN WHAT APPEARS TO
 BECAF? 11D03 ANDCOPY 11E03. THESE CONTAIN AN *82*
 HOWEVER NO OTHER CONTROL DESIGNATION WAS LOCATED.
 PLEASE SEE THE FOLLOWING NOTE WITH RESPECT TO
 CIRCUITING AS THIS AFFECTS SOME *K* FIXTURES AS WELL.
  
 4) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS AND
 PANEL SCHEDULES. THIS AFFECT THE LIGHTING CONTROLS AS
 WELL. FOR SOME EXAMPLES PLEASE SEE THE FOLLOWING.
 PLEASE SEE ROOM 11H06 WHICH CONTAINS *K* FIXTURES,
 THESE ARE SHOWN CIRCUITED IN TWO LOCATIONS AND BOTH
 SHOW THE SAME CIRCUIT P2102-28. THIS CIRCUIT AS SHOWN
 IN THE PANEL P2102 IS FOR ROOM 11D03 WATER DISPENSER.
 PLEASE SEE ROOM/AREA RIGHT OUTSIDE OF COPY ROOM 11E03
 WHICH CONTAINS CIRCUITING P211-82. NO PANEL P211 COULD
 BE LOCATED ON PLANS.ONLY TWO PANEL SCHEDULES WHICH
 CONTAIN SUB-SECTIONS WHICH DO CONTAIN A CIRCUIT/SPACE
 82 ARE SHOWN AS SPARES/SPACE WITH NOT INDICATION OF
 LIGHTING.
 PLEASE SEE THE OTHER FIXTURES IN THIS AREA WHICH ARE
 ALSO LABELED WITH THE SAME 82.
 ** AS MENTION ON PREVIOUS REVIEW AND IN MEETING HELD
 THESE ARE SOME EXAMPLES. PLEASE GO OVER ALL CIRCUITING
 AND COORDINATE WITH PANEL SCHEDULES, CONTROLS ETC.
 408.4, 240.4, 310.16.
 FBC 13-415.1.ABC.1.1, .1.2, .1.3 (AS NOTED ABOVE) FBC
 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE FP SHEETS WHICH ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER. THE SHEET
 ATTACHED TO THESE SHEETS MAY NOT BE USED TO TAKE PLACE
 OF THE REQUIRED INFORMATION ON TITLE BLOCKS OF SIGNED
 AND SEALED PLANS. THIS INFORMATION MAY BE PRINTED ON
 SHEETS AND IS BEING GIVEN AS INFORMATION AT THIS TIME.
 THIS COMMENT IS NOT FOR AHA.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  