| 2007-09-12 09:45:13 | 2007-09-12 09:45:13 |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | *** PLEASE KNOW THAT AS SOME ITEMS FROM THE PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. ** PLEASE |
| | SEE THERE ARE ALSO SOME NEW COMMENTS, BASED ON CHANGES |
| | AND INFORMATION NOW SHOWN ON PLANS. THERE IS ONE NEW |
| | COMMENT FOR ITEM MISSED ON PREVIOUS REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE MISSING PRINTED NAME ON THE |
| | ENGINEERING SHEETS FOR THE ENGINEER OF RECORD AS |
| | REQUIRED PER FAC 61G15-23.002. |
| | PLEASE ALSO SEE THE ENGINEER OF RECORD IS ALSO REQUIRES |
| | DATING PLANS WHEN SIGNING WHICH WAS NOT DONE ON ALL |
| | SETS. PLEASE ALSO BE SURE ALL LICENSE INFORMATION PER |
| | FAC 61G15-23.002, FS 471.025 |
| | |
| | 2) NOTE: PLEASE SEE IT IS STILL UNCLEAR WHAT FLOOR WORK |
| | IS BEING DONE ON. THE ORIGINAL PLANS FOR BASE BUILDING |
| | CLEARLY INDICATE THE EXISTING PANELS ON RISER WHICH ARE |
| | L410A, P210A M410A ETC ON THE 10TH FLOOR YET THESE |
| | PLANS AND TITLE BLOCK CALLS THIS THE 11TH FLOOR. THE |
| | PLANS FOR LIGHTING AND POWER CALL FOR THE 11TH FLOOR, |
| | YET THE PLANS ALSO CALL FOR THE 10TH FLOOR. THIS IS |
| | CONFUSING WHY A 10TH FLOOR WOULD BE CALLED THE 11TH |
| | FLOOR AND ALL DESIGNATIONS FOR ROOMS AND AREAS ARE |
| | SHOWN WITH 11/ELEVEN DESIGNATIONS IF THIS IS THE 10TH |
| | FLOOR. THE BASE BUILDING PLANS CALL THIS SAME FLOOR 10 |
| | AND NOT 11? |
| | PLEASE CLARIFY |
| | FAC 61G1-16.004 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY |
| | CALCULATIONS SUBMITTED. PLEASE SEE POSSIBLE MECHANICAL |
| | REVIEW COMMENTS FOR METHOD. |
| | PLEASE KNOW IN EITHER CASE THE ENERGY CALCULATIONS AS |
| | SUBMITTED DO NOT CORRELATE WITH THE SUBMITTED LIGHTING |
| | ON PLANS. THE INPUT DATA REPORT WILL BE ABBREVIATED AS |
| | IDR FOR THE REST OF THESE NOTES. |
| | PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS (OVER |
| | 100) WHICH ARE NOT INCLUDED ON THE INPUT DATA REPORT. |
| | PLEASE SEE THE PREVIOUS REVIEW NOTES WHICH REQUESTED |
| | FOR THE ROOM AND AREA DESIGNATIONS ON PLANS TO BE |
| | IDENTIFIED ON THE IDR FOR REVIEW AS THERE WERE MULTIPLE |
| | ROOMS AND AREAS WITH THE SAME DESIGNATIONS. THE ONLY |
| | WAY TO IDENTIFY A ROOM OR AREA IS TO GO THROUGH THE |
| | FIXTURE LEGEND AND COUNT EACH FIXTURE IN A ROOM WHICH |
| | MAY OR MAY NOT ADD UP TO THE INFORMATION ON THE IDR. |
| | PLEASE SEE THE CONFERENCE ROOM FOR ONE EXAMPLE. THIS IS |
| | SHOWN AS CONF ON THE IDR AND THERE ARE MULTIPLE ROOMS |
| | OF THE SAME DESIGNATION.IN EITHER CASE PLEASE SEE |
| | CONFERENCE ROOMS IDENTIFIED ON PLANS AS 11L09 AND 11L08 |
| | BOTH OF WHICH CONTAIN THE SAME AMOUNT AND TYPE OF |
| | FIXTURES, YET NEITHER CORRELATE WITH ANY OF THE |
| | CONFERENCE ROOMS ON THE IDR FOR THE NUMBER AND TYPE OF |
| | FIXTURES. |
| | THIS IS ONLY ONE EXAMPLE AS THERE ARE NUMEROUS OTHER |
| | ROOMS WHICH THE LIGHTING ON PLANS DOES NOT MATCH WITH |
| | THE IDR. |
| | PLEASE SEE THERE ARE FIXTURES ON PLANS AND FIXTURE |
| | LEGEND WHICH ARE NOT ON THE IDR. EXAMPLE: SEE |
| | FIXTURE*J*. THIS IS ONLY ONE AS NOTED AND THERE ARE |
| | OTHERS. |
| | THE PLANS INDICATE A TOTAL OF 60+/PLUS ROOMS AND AREAS, |
| | YET THE IDR ONLY INDICATES 30+/-. WHERE ARE THE OTHER |
| | ROOMS, AREAS, LIGHTING FIXTURES ETC.? |
| | PLEASE COORDINATED ALL ON PLANS WITH THE INPUT DATA |
| | REPORT AND ENERGY CALCULATIONS.13-415.1.A, 13-415.1.B , |
| | 13-415.1.C, 13-415.2. |
| | FBC 106.3.5.1.2, 106.1.2, ETC |
| | |
| | 4) NOTE: PLEASE SEE THERE IS STILL NOT ENOUGH |
| | INFORMATION SHOWN FOR LIGHTING CONTROLS, DEVICES, |
| | SYSTEM ETC. THERE ARE NUMEROUS LOCATIONS WHERE NO |
| | CONTROLS FOR LIGHTING COULD BE LOCATED OR FOUND. PLEASE |
| | SEE THERE ARE MISSING CONTROLS REQUIRED PER |
| | 13-415.1.ABC.1.3. |
| | |
| | 5) NOTE: PLEASE SEE THE TRANSFORMER LISTED AS T4A HAS |
| | OVER CURRENT PROTECTION SET ABOVE PERMITTED MAXIMUM |
| | LEVELS PER 450.3. THIS WAS NOT NOTED ON PREVIOUS REVIEW |
| | HOWEVER PLEASE CORRECT PER 450.3.MUST MEET NOTE #5 IF |
| | EXCEEDING THE MAXIMUM OF 125%, IF THIS IS THE CASE |
| | PLEASE PROVIDE THE INFORMATION ON THE TRANSFORMER AS |
| | NEEDED. 90.7, 110.3 |
| | |
| | 6) NOTE: PLEASE VERIFY THE PANEL DP10. IT WAS THE |
| | UNDERSTANDING THAT EACH TENANT WOULD CONTAIN A MAIN |
| | WHICH WOULD BE ABLE TO TURN OFF ALL POWER TO THEIR |
| | SPACE. |
| | THIS IS SAME FOR THE BRANCH CIRCUITS COMING FROM OTHER |
| | PANELS AND OTHER FLOORS SPECIFICALLY THE CIRCUITING |
| | INTO THE TENANT SPACE FOR 277V LIGHTING. IS THERE A |
| | DISCONNECT SWITCH OF SOME KIND FOR THE LIGHTING INTO |
| | SPACE? |
| | PLEASE SEE CONSTRUCTION BOARD OF APPEALS PROPOSED OWNER |
| | SET UP FOR EACH TENANT WHICH HAD AN AGREEMENT OF TENANT |
| | BEING ABLE TO TURN OFF POWER IN AN EMERGENCY? |
| | |
| | 7) NOTE: PLEASE CLARIFY THE DP10 WHICH SHOWS A 125AMP |
| | MCB FEEDING PANEL L410 WHICH IS A 100AMP RATED PANEL |
| | WITH A 100AMP MCB? THIS WAS NOTED ON PREVIOUS REVIEW |
| | HOWEVER THE PANEL DESIGNATION HAS CHANGED. |
| | FBC 106.1.2 FOR INFORMATION. |
| | |
| | 8) NOTE: PLEASE SEE THE NEW LOCATION OF THE ELECTRICAL |
| | TRANSFORMERS, PANELS AND ELECTRICAL SERVICE EQUIPMENT |
| | IS NOW BEING SHOWN IN THE FILE STORAGE ROOM WHICH IS |
| | NOT PERMITTED. |
| | PLEASE PROVIDE A SAFE, SECURE, RATED LOCATION AS |
| | REQUIRED FOR LIFE SAFETY, FIRE HAZARD AND PROPERTY |
| | HAZARD. |
| | 240.24D, 110.26, 110.27, 408.17 |
| | |
| | 9) NOTE: PLEASE CLARIFY SOME FIXTURE AND RECEPTACLE |
| | LOCATIONS WHICH STILL CONTAIN ALPHA AND NUMERIC |
| | DESIGNATIONS HOWEVER IT IS UNCLEAR WHAT THESE ARE? FBC |
| | 106.1.2 |
| | |
| | 10) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES. PLEASE SEE THERE |
| | ARE STILL RECEPTACLES ON PLANS WHICH DO NOT CONTAIN ANY |
| | CIRCUIT DESIGNATIONS. PLEASE SEE THERE ARE SOME WHICH |
| | CONTAIN A NUMERICAL IDENTIFICATION HOWEVER THERE IS NOT |
| | PANEL DESIGNATION. THERE ARE AREAS WHICH CONTAIN THE |
| | NUMERIC DESIGNATIONS AND CLOSE BY HAS THE SAME CIRCUIT |
| | NUMBER WITH OTHER WHICH NOTES TO WHICH PANEL THESE GO |
| | TO HOWEVER PLEASE SEE REDLINED PLANS FOR LOCATIONS |
| | MISSING. |
| | PLEASE SEE SOME ROOMS FOR EXAMPLE: 11J09, 11L08, 11L09, |
| | 11J06 FOR A FEW WHICH INDICATE A NUMERICAL DESIGNATIONS |
| | YET THE PANEL CIRCUITING LOCATED IN CLOSE PROXIMITY |
| | COULD BE FOR TWO DIFFERENT PANELS. PLEASE ALSO SEE TWO |
| | RECEPTACLES WITH ONE NUMERICAL CIRCUIT DESIGNATION ROOM |
| | 11L09 NORTH WALL. |
| | PLEASE SEE ROOM 11J14 WHICH DOES NOT INDICATE ANY |
| | RECEPTACLES, YET THE DESIGNATIONS IS OFFICE. A NOTE ON |
| | PLAN MENTIONS *TYP* FOR TYPICAL, HOWEVER THIS IS |
| | TYPICAL OF WHAT? |
| | PLEASE GO OVER ALL CIRCUITING ON PLANS AND BE SURE TO |
| | COORDINATE WITH THE PANEL SCHEDULES. |
| | 408.4 |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE PANEL SCHEDULE FOR P2102 WHICH |
| | SHOWS THIS AS BEING *SECTION #1*. IS THERE ARE SECTION |
| | #2? THIS APPEARS TO BE A MISPRINT AS RISER AND PLANS |
| | DOES NOT SHOW ANY SECTION #2. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW THAT PLANS MAY BE RETAINED BY THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2007-09-12 07:03:23 | 2007-09-12 07:03:23 |
| | |
| | IN PROGRESS |
| 2007-09-11 20:07:00 | 2007-09-11 20:07:01 |
| | |
| | REVIEW TO CONTINUE ON 9/12, NOTES WILL FOLLOW ONCE |
| | REVIEW IS COMPLETED. |
| 2007-09-11 18:17:48 | 2007-09-11 18:17:48 |
| | |
| | IN ELEC FOR REVIEW. |