Plan Review Notes
Plan Review Notes For Permit 07050059
Permit Number 07050059
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-12 09:45:132007-09-12 09:45:13
  
 ** DENIED 2ND REVIEW **
  
 *** PLEASE KNOW THAT AS SOME ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. ** PLEASE
 SEE THERE ARE ALSO SOME NEW COMMENTS, BASED ON CHANGES
 AND INFORMATION NOW SHOWN ON PLANS. THERE IS ONE NEW
 COMMENT FOR ITEM MISSED ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE MISSING PRINTED NAME ON THE
 ENGINEERING SHEETS FOR THE ENGINEER OF RECORD AS
 REQUIRED PER FAC 61G15-23.002.
 PLEASE ALSO SEE THE ENGINEER OF RECORD IS ALSO REQUIRES
 DATING PLANS WHEN SIGNING WHICH WAS NOT DONE ON ALL
 SETS. PLEASE ALSO BE SURE ALL LICENSE INFORMATION PER
 FAC 61G15-23.002, FS 471.025
  
 2) NOTE: PLEASE SEE IT IS STILL UNCLEAR WHAT FLOOR WORK
 IS BEING DONE ON. THE ORIGINAL PLANS FOR BASE BUILDING
 CLEARLY INDICATE THE EXISTING PANELS ON RISER WHICH ARE
 L410A, P210A M410A ETC ON THE 10TH FLOOR YET THESE
 PLANS AND TITLE BLOCK CALLS THIS THE 11TH FLOOR. THE
 PLANS FOR LIGHTING AND POWER CALL FOR THE 11TH FLOOR,
 YET THE PLANS ALSO CALL FOR THE 10TH FLOOR. THIS IS
 CONFUSING WHY A 10TH FLOOR WOULD BE CALLED THE 11TH
 FLOOR AND ALL DESIGNATIONS FOR ROOMS AND AREAS ARE
 SHOWN WITH 11/ELEVEN DESIGNATIONS IF THIS IS THE 10TH
 FLOOR. THE BASE BUILDING PLANS CALL THIS SAME FLOOR 10
 AND NOT 11?
 PLEASE CLARIFY
 FAC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY
 CALCULATIONS SUBMITTED. PLEASE SEE POSSIBLE MECHANICAL
 REVIEW COMMENTS FOR METHOD.
 PLEASE KNOW IN EITHER CASE THE ENERGY CALCULATIONS AS
 SUBMITTED DO NOT CORRELATE WITH THE SUBMITTED LIGHTING
 ON PLANS. THE INPUT DATA REPORT WILL BE ABBREVIATED AS
 IDR FOR THE REST OF THESE NOTES.
 PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS (OVER
 100) WHICH ARE NOT INCLUDED ON THE INPUT DATA REPORT.
 PLEASE SEE THE PREVIOUS REVIEW NOTES WHICH REQUESTED
 FOR THE ROOM AND AREA DESIGNATIONS ON PLANS TO BE
 IDENTIFIED ON THE IDR FOR REVIEW AS THERE WERE MULTIPLE
 ROOMS AND AREAS WITH THE SAME DESIGNATIONS. THE ONLY
 WAY TO IDENTIFY A ROOM OR AREA IS TO GO THROUGH THE
 FIXTURE LEGEND AND COUNT EACH FIXTURE IN A ROOM WHICH
 MAY OR MAY NOT ADD UP TO THE INFORMATION ON THE IDR.
 PLEASE SEE THE CONFERENCE ROOM FOR ONE EXAMPLE. THIS IS
 SHOWN AS CONF ON THE IDR AND THERE ARE MULTIPLE ROOMS
 OF THE SAME DESIGNATION.IN EITHER CASE PLEASE SEE
 CONFERENCE ROOMS IDENTIFIED ON PLANS AS 11L09 AND 11L08
 BOTH OF WHICH CONTAIN THE SAME AMOUNT AND TYPE OF
 FIXTURES, YET NEITHER CORRELATE WITH ANY OF THE
 CONFERENCE ROOMS ON THE IDR FOR THE NUMBER AND TYPE OF
 FIXTURES.
 THIS IS ONLY ONE EXAMPLE AS THERE ARE NUMEROUS OTHER
 ROOMS WHICH THE LIGHTING ON PLANS DOES NOT MATCH WITH
 THE IDR.
 PLEASE SEE THERE ARE FIXTURES ON PLANS AND FIXTURE
 LEGEND WHICH ARE NOT ON THE IDR. EXAMPLE: SEE
 FIXTURE*J*. THIS IS ONLY ONE AS NOTED AND THERE ARE
 OTHERS.
 THE PLANS INDICATE A TOTAL OF 60+/PLUS ROOMS AND AREAS,
 YET THE IDR ONLY INDICATES 30+/-. WHERE ARE THE OTHER
 ROOMS, AREAS, LIGHTING FIXTURES ETC.?
 PLEASE COORDINATED ALL ON PLANS WITH THE INPUT DATA
 REPORT AND ENERGY CALCULATIONS.13-415.1.A, 13-415.1.B ,
 13-415.1.C, 13-415.2.
 FBC 106.3.5.1.2, 106.1.2, ETC
  
 4) NOTE: PLEASE SEE THERE IS STILL NOT ENOUGH
 INFORMATION SHOWN FOR LIGHTING CONTROLS, DEVICES,
 SYSTEM ETC. THERE ARE NUMEROUS LOCATIONS WHERE NO
 CONTROLS FOR LIGHTING COULD BE LOCATED OR FOUND. PLEASE
 SEE THERE ARE MISSING CONTROLS REQUIRED PER
 13-415.1.ABC.1.3.
  
 5) NOTE: PLEASE SEE THE TRANSFORMER LISTED AS T4A HAS
 OVER CURRENT PROTECTION SET ABOVE PERMITTED MAXIMUM
 LEVELS PER 450.3. THIS WAS NOT NOTED ON PREVIOUS REVIEW
 HOWEVER PLEASE CORRECT PER 450.3.MUST MEET NOTE #5 IF
 EXCEEDING THE MAXIMUM OF 125%, IF THIS IS THE CASE
 PLEASE PROVIDE THE INFORMATION ON THE TRANSFORMER AS
 NEEDED. 90.7, 110.3
  
 6) NOTE: PLEASE VERIFY THE PANEL DP10. IT WAS THE
 UNDERSTANDING THAT EACH TENANT WOULD CONTAIN A MAIN
 WHICH WOULD BE ABLE TO TURN OFF ALL POWER TO THEIR
 SPACE.
 THIS IS SAME FOR THE BRANCH CIRCUITS COMING FROM OTHER
 PANELS AND OTHER FLOORS SPECIFICALLY THE CIRCUITING
 INTO THE TENANT SPACE FOR 277V LIGHTING. IS THERE A
 DISCONNECT SWITCH OF SOME KIND FOR THE LIGHTING INTO
 SPACE?
 PLEASE SEE CONSTRUCTION BOARD OF APPEALS PROPOSED OWNER
 SET UP FOR EACH TENANT WHICH HAD AN AGREEMENT OF TENANT
 BEING ABLE TO TURN OFF POWER IN AN EMERGENCY?
  
 7) NOTE: PLEASE CLARIFY THE DP10 WHICH SHOWS A 125AMP
 MCB FEEDING PANEL L410 WHICH IS A 100AMP RATED PANEL
 WITH A 100AMP MCB? THIS WAS NOTED ON PREVIOUS REVIEW
 HOWEVER THE PANEL DESIGNATION HAS CHANGED.
 FBC 106.1.2 FOR INFORMATION.
  
 8) NOTE: PLEASE SEE THE NEW LOCATION OF THE ELECTRICAL
 TRANSFORMERS, PANELS AND ELECTRICAL SERVICE EQUIPMENT
 IS NOW BEING SHOWN IN THE FILE STORAGE ROOM WHICH IS
 NOT PERMITTED.
 PLEASE PROVIDE A SAFE, SECURE, RATED LOCATION AS
 REQUIRED FOR LIFE SAFETY, FIRE HAZARD AND PROPERTY
 HAZARD.
 240.24D, 110.26, 110.27, 408.17
  
 9) NOTE: PLEASE CLARIFY SOME FIXTURE AND RECEPTACLE
 LOCATIONS WHICH STILL CONTAIN ALPHA AND NUMERIC
 DESIGNATIONS HOWEVER IT IS UNCLEAR WHAT THESE ARE? FBC
 106.1.2
  
 10) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES. PLEASE SEE THERE
 ARE STILL RECEPTACLES ON PLANS WHICH DO NOT CONTAIN ANY
 CIRCUIT DESIGNATIONS. PLEASE SEE THERE ARE SOME WHICH
 CONTAIN A NUMERICAL IDENTIFICATION HOWEVER THERE IS NOT
 PANEL DESIGNATION. THERE ARE AREAS WHICH CONTAIN THE
 NUMERIC DESIGNATIONS AND CLOSE BY HAS THE SAME CIRCUIT
 NUMBER WITH OTHER WHICH NOTES TO WHICH PANEL THESE GO
 TO HOWEVER PLEASE SEE REDLINED PLANS FOR LOCATIONS
 MISSING.
 PLEASE SEE SOME ROOMS FOR EXAMPLE: 11J09, 11L08, 11L09,
 11J06 FOR A FEW WHICH INDICATE A NUMERICAL DESIGNATIONS
 YET THE PANEL CIRCUITING LOCATED IN CLOSE PROXIMITY
 COULD BE FOR TWO DIFFERENT PANELS. PLEASE ALSO SEE TWO
 RECEPTACLES WITH ONE NUMERICAL CIRCUIT DESIGNATION ROOM
 11L09 NORTH WALL.
 PLEASE SEE ROOM 11J14 WHICH DOES NOT INDICATE ANY
 RECEPTACLES, YET THE DESIGNATIONS IS OFFICE. A NOTE ON
 PLAN MENTIONS *TYP* FOR TYPICAL, HOWEVER THIS IS
 TYPICAL OF WHAT?
 PLEASE GO OVER ALL CIRCUITING ON PLANS AND BE SURE TO
 COORDINATE WITH THE PANEL SCHEDULES.
 408.4
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE FOR P2102 WHICH
 SHOWS THIS AS BEING *SECTION #1*. IS THERE ARE SECTION
 #2? THIS APPEARS TO BE A MISPRINT AS RISER AND PLANS
 DOES NOT SHOW ANY SECTION #2.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THAT PLANS MAY BE RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2007-09-12 07:03:232007-09-12 07:03:23
  
 IN PROGRESS
2007-09-11 20:07:002007-09-11 20:07:01
  
 REVIEW TO CONTINUE ON 9/12, NOTES WILL FOLLOW ONCE
 REVIEW IS COMPLETED.
2007-09-11 18:17:482007-09-11 18:17:48
  
 IN ELEC FOR REVIEW.