| 2007-09-19 11:26:20 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050059 |
| | ADD: 525 OKEECHOBEE BLVD SUITE# 1100 |
| | CONT: BALFOUR BEATTY CONSTRUCTION |
| | TEL: (561)478-0381 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT |
| | STATEMENT --- |
| | PLEASE DO NOT |
| | IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3-6) COMPLIED. |
| | |
| | 7)SECOND REQUEST, CAF? AND CATERING ROOM SHEET A012.04 |
| | DETAIL# 6, THE DETAIL INDICATES THE USE OF DOORS IN |
| | FRONT OF THE ACCESSIBLE SINK, THESE DOORS NEED TO BE |
| | REMOVED FOR A FRONTAL APPROACH. WITH DOORS ON THE |
| | CABINET THERE WILL BE A TENDENCY TO STORE ITEMS ON THE |
| | FLOOR THAT WOULD NOT ALLOW ACCESSIBILITY. |
| | SINKS. SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A |
| | SINK TO ALLOW FORWARD APPROACH. THE CLEAR FLOOR SPACE |
| | SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL EXTEND A |
| | MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE SINK. |
| | |
| | 8) NEW COMMENT, DEALS WITH THE STRUCTURAL SHEET, SINCE |
| | THE NEW STRUCTURAL BEAM IS NOT |
| | GOING TO BE A REVISION UNDER THE BASE BUILDING THE |
| | FOLLOWING INFORMATION WILL BE REQUIRED: |
| | 8A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL |
| | INSPECTION PLAN" |
| | PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 8B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE |
| | OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT |
| | SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR |
| | THE " BASE BUILDING" |
| | AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE |
| | APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS |
| | PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN |
| | ISSUED. |
| | |
| | 8C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS, |
| | THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW |
| | AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH |
| | THEIR APPROVAL. |
| | |
| | 8D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR |
| | ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER |
| | DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF |
| | THIS PERMIT. |
| | |
| | 8E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO |
| | INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3 |
| | HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE |
| | SPRINKLED BUILDINGS. |
| | PLEASE SHOW COMPLIANCE. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |