| 2007-06-02 14:02:23 | -----------------DENIED----------------- |
| | |
| | FBC 2004 CODE FAMILY W/ 2006 REVISIONS |
| | FBC 2004 CH.1 AS AMENDED BY THE CITY OF WEST PALM |
| | BEACH |
| | |
| | 1.PLEASE VERIFY VALUES ON FPT SCHEDULE. EXAMPLES: A) |
| | FPT-11-1 HAS A 12" ROUND INLET, BUT PLAN SHOWS IT BEING |
| | FED BY A 16" ROUND DUCT. |
| | B) FPT-11-3 MAX FAN CFM AS SHOWN IS OUTSIDE THE CFM |
| | RANGE FOR A TITUS DTQS 2-8. |
| | C) FPT-11-4 IS SHOWN ON PLANS SUPPLYING 740 CFM, BUT |
| | SHCEDULE SHOWS MAX FAN CFM AT 680. |
| | PLEASE CLARIFY ALL DISCREPENCIES IN THIS SCHEDULE AND |
| | CORRELATE WITH FLOOR PLAN. EQUIPMENT AND APPLIANCES |
| | SHALL BE INSTALLED IN ACCORDANCE WITH THEIR LISTING AND |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS PER FBC,M |
| | 304.1. |
| | |
| | 2. I.T. ROOM 11J05: PLAN SHOWS ALL SUPPLY AIR BEING |
| | RECIRCULATED TO PLENUM SPACE BY EF-11-1 THROUGH AN |
| | EXHAUST GRILL LOCATED IN THE CEILING. WHAT IS THE |
| | PURPOSE OF THE TWO 24X24 LAY-IN RETURN GRILLS IN THE |
| | CEILING? |
| | |
| | 3. EF-11-1 DISCHARGES INDOORS. THEREFORE IT IS NOT AN |
| | EXHAUST FAN. PLEASE CHANGE THE DESIGNATION OF THIS FAN |
| | SO AS NOT TO BE IN CONFLICT WITH FBC,M 501.2. |
| | |
| | 4. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS TO SHOW |
| | COMPLIANCE WITH FBC,M 403.2. |
| | |
| | 5. EXTERIOR WALLS EXPOSED TO CEILING PLENUM ARE TO BE |
| | INSULATED TO A MINIMUM VALUE OF R-8 AND LINED WITH AN |
| | APPROVED AIR BARRIER PER FBC 13-410.1.ABC.3.6. ALSO SEE |
| | 410.1.ABC.2.2 AND 410.1.ABC.3.7. THE AIR BARRIER |
| | PROVISIONS ALSO APPLY TO INTERIOR WALLS BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. |
| | NOTE: ENERGY CALCULATIONS SHOW EXTERIOR WALLS ARE |
| | CURRENTLY INSULATED TO A VALUE OF R-4.8. |
| | |