| 2007-06-05 16:14:02 | ** UNSAT ** |
| | |
| | *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR |
| | CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT |
| | YET ABLE TO BE MADE. |
| | |
| | 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE |
| | UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER |
| | 8TH, 2006. |
| | PLEASE THE ARCHITECTURAL SHEETS INDICATE SOME OLDER |
| | CODES AS WELL AS THE ELECTRICAL SHEETS WHICH INDICATE |
| | SOME OF THE PREVIOUS CODES. SOME OF THE NOTES ON THE |
| | ELECTRICAL SHEETS DO INDICATE THE NEWER ADOPTED CODES. |
| | |
| | 2004 FBC W/2006 REVISIONS (ARCH AND ELECTRICAL SHEETS) |
| | 2005 NFPA?70 (NEC) (ARCH AND ELECTRICAL SHEETS) THE |
| | OTHER CODES AS LISTED ARE OK. PLEASE BE SURE TO SEE |
| | OTHER TRADES FOR COMMENTS ON ANY CODE ADJUSTMENTS. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON THE |
| | TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AND ARCHITECT. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FLORIDA STATUTES 481.219 |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER FOR FIRM, |
| | PRINTED NAME OF ARCHITECT AND PRINTED LICENSE NUMBER. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | |
| | 3) NOTE: PLEASE SEE THE ARCHITECT DID NOT DATE PLANS |
| | WHEN SIGNED AS REQUIRED PER FS 481.221. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS IN SOME NOTES INDICATE |
| | WORK FOR *CARLTON FIELDS* WHICH IS WORK BEING DONE FOR |
| | ANOTHER TENANT BUILD-OUT ON ANOTHER FLOOR. REDLINED AT |
| | LOCATIONS. |
| | PLEASE ADJUST. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER HAS BEEN |
| | ISSUED/ASSESSED AS 1100, PLEASE INCLUDE ON PLANS AS |
| | THERE WILL BE MORE THAN ONE TENANT ON FLOOR WITH MORE |
| | THAN ONE SUITE/UNIT. |
| | AFC 61G1-16.004 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR THE |
| | AHA ENGINEERING FIRM DOES NOT COORDINATE WITH THAT AS |
| | LISTED WITH THE FLORIDA DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. |
| | ** THE ADDRESS OF THE SATELLITE OFFICE IS OK, HOWEVER |
| | PLEASE LIST THE PRIMARY HOME OFFICE AS LICENSED. |
| | |
| | 7) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE SCOPE OF WORK |
| | WILL BE UNDER SEPARATE PERMITS. THE PHONE, CATV, ACCESS |
| | CONTROL SYSTEM ETC. PERMITS FOR OTHER THAN SECURITY CAN |
| | REFERENCE BACK TO THESE PLANS FOR PERMIT HOWEVER THE |
| | VALUE AND PERMIT FEE IS BASED ON THAT SCOPE OF WORK. |
| | THE ACCESS CONTROL SYSTEM/SECURITY WILL REQUIRE PLANS |
| | AND SUBMITTALS FOR DEVICES FOR ACCESS CONTROL. * PLEASE |
| | KNOW THAT THESE DEVICES MAY NOT IMPEDED EGRESS FROM |
| | BUILDING IN THE EVENT OF AN EMERGENCY PER LS 101 CODE. |
| | |
| | 8) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY |
| | CALCULATIONS SUBMITTED AS THE VERSION ADOPTED AS OF |
| | DECEMBER 8TH, 2006 IS NOT THAT AS SUBMITTED. (3.0). |
| | PLEASE SEE THE CALCULATIONS NEED TO BE SIGNED BY THE |
| | OWNER'S AGENT AS STATED ON SHEETS. (CONTRACTOR). PLEASE |
| | COORDINATE ALL OF THE TYPES OF FIXTURES, THE NUMBER OF |
| | FIXTURES ON THE CALCULATIONS WITH THAT OF THE FIXTURES |
| | ON PLANS AND FIXTURE LEGEND. THERE ARE SOME |
| | DISCREPANCIES BETWEEN THE THREE. |
| | PLEASE LABEL THE ROOMS ON CALCULATIONS AS THE |
| | DESIGNATIONS ON PLANS OR TO THE POINT EACH ROOM WHICH |
| | CONTAINS THE SAME NAME OR CURRENTLY THE SAME |
| | DESCRIPTION FOR MULTIPLE ROOMS CAN BE DIFFERENTIATED. |
| | PLEASE SEE FBC CHAPTER 13 2004 W/2006 REVISIONS |
| | 13-415.1.AB.1.1, .1.2, 13-415.2, 13-103.1.1.1 ETC. |
| | |
| | 9) NOTE: PLEASE SEE THE TRANSFORMER LIST WHICH |
| | INDICATES 400AMP OCP ON THE PRIMARY SIDE OF THE T8A |
| | WHICH DOES NOT MEET 450.3. PLEASE SEE THAT IF THE |
| | TRANSFORMER IS NOT GOING TO BE PART OF THIS BUILDING |
| | REMOVE OR CORRECT OCP SIZE. |
| | |
| | 10) NOTE: PLEASE SEE THE TRANSFORMER LEGEND DOES NOT |
| | CORRELATE WITH THAT OF THE RATING OF THE TRANSFORMER |
| | INDICATED ON DP1. |
| | PLEASE COORDINATE AND ADJUST AS NEEDED. |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE ELECTRICAL ROOM CONTAINS |
| | EQUIPMENT WHICH IS NOT LISTED OR SHOWN ON RISER OR |
| | PANEL SCHEDULES SUBMITTED, PLEASE COMPLETE. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 215.5, 408.4, 310.16, 240.4 ETC |
| | |
| | 12) NOTE: PLEASE SEE THE RISER INDICATE THE ELECTRICAL |
| | ROOM LOCATED ON THE 10TH FLOOR AND THE PLANS INDICATE |
| | THIS ON THE SAME FLOOR AS THE TENANT SPACE?? PLEASE |
| | CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SEE THE EMERGENCY LIGHTING AND EXIT |
| | LIGHTS DO NOT MEET 700.12F |
| | ALSO INDICATES THESE BEING FED FROM THE EMERGENCY PANEL |
| | ON THE 11TH FLOOR, HOWEVER THIS BUILD OUT IS FOR THE |
| | 11TH FLOOR. AS THE RISER AND PLANS DO NOT MATCH AND THE |
| | CIRCUITING IS NOT CORRECT IT IS UNCLEAR WHAT IS BEING |
| | DONE. |
| | PLEASE ALSO EXPLAIN THE EMERGENCY LIGHTING DETAIL AS |
| | INDICATED ON E1.11. |
| | |
| | 14) NOTE: PLEASE SEE PANEL L411AS THIS IS A 100AMP |
| | RATED PANEL WITH 125AMP BREAKER FEEDING THIS PANEL? |
| | PLEASE CLARIFY AND EXPLAIN. |
| | FBC 106.1.2, |
| | NEC 240, 408,ETC |
| | |
| | 15) NOTE: PLEASE SEE THE CORRIDORS WHICH ARE BEING |
| | SHOWN ON THESE PLANS AS EXISTING DO NOT EXISTING UNDER |
| | THE BASE BUILDING AND ARE NOT BEING APPLIED FOR UNDER |
| | THE BUILD OUT PERMIT. THIS WAS IN THE CONDITION OF |
| | ISSUANCE OF MAIN BUILDING PERMIT AND CONTRACTOR ALONG |
| | WITH OWNER SAID THIS WORK WOULD BE PERMITTED BEFORE |
| | BUILD OUTS; HOWEVER THIS IS NOT THE CASE. |
| | PLEASE SEE FBC 106, 104, 105 FOR WORK REQUIRED TO HAVE |
| | PERMITS. |
| | |
| | 16) NOTE: PLEASE CLARIFY SOME FIXTURES WHICH CONTAIN |
| | LETTERING OF SOME KIND WHICH COULD NOT LOCATE |
| | DESIGNATIONS OR ANY NOTES FOR WHAT SOME OF THESE ARE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 17) NOTE: PLEASE SEE THAT ANY CHANGES ON THE BUILD OUT |
| | PLANS NEEDS TO BE INCORPORATED INTO THE BASE BUILDING |
| | PLANS. PLEASE COORDINATE FOR LOADS, CALCULATIONS, ETC. |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES. |
| | FBC 106.3.5.1.2 |
| | |
| | 19) NOTE: PLEASE PROVIDE THE MINIMUM LAYOUT FOR ALL FA |
| | DEVICES FOR HORNS AND STROBES PER FBC 11-4.28.1,.2 AND |
| | .3(4). THE LEVELS ARE INDICATE ON THE SYMBOL LEGEND |
| | HOWEVER THE BASE BUILD OUT PLANS ARE REQUIRED TO SHOW |
| | THE MINIMUM LOCATIONSFOR FBC COMPLIANCE EVEN IF |
| | THOUGH THE FIRE ALARM AND ANY FIRE SPRINKLER PERMITS |
| | ARE DONE SEPARATELY AS REQUIRED. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 20) NOTE: PLEASE CLARIFY THE ROOM LABELED AS *IT* |
| | ROOM.; IF THIS IS INDEED A TRUE IT ROOM AS DEFINED IN |
| | THE NEC 645 AND NFPA-75, THEN PLEASE ADJUST PLANS TO |
| | MEET THE MINIMUM REQUIREMENTS FOR BUILDING, ELECTRICAL |
| | AND ANY MECHANICAL. |
| | IF THIS IS NOT A TRUE IT ROOM BY DEFINITIONS, PLEASE |
| | REMOVE THIS DESIGNATION FROM PLANS. |
| | |
| | 21) NOTE: PLEASE SEE NOTES MENTIONS THE MAINSHUNT |
| | TRIP RATED SWITCH WILL BE 600AMP RATED YET RISER SHOWS |
| | 400AMP. PLEASE CORRELATE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |