| 2007-06-18 13:16:44 | BUILDING PLAN REVIEW |
| | PERMIT: 07050059 |
| | ADD: 525 OKEECHOBEE BLVD # 1100 |
| | CONT: BALFOUR BEATTY CONST |
| | TEL: (561)478-0381 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) SHEET 00.000 CODE SUMMARY INDICATES THE DESIGN IS |
| | THE FBC 2004, PLEASE INDICATE THE CODE UPDATES PLANS |
| | SUBMITTED AFTER DEC.8/06 SHOULD HAVE BEEN DESINED TO |
| | THE 2004 FBC WITH 2006 AMENDMENTS. |
| | |
| | 4A) A012.02 DOOR DETAILS PLEASE SHOW FIRE TREATED WOOD |
| | BUCKS. SECTION 603. |
| | |
| | 4B) THE DOUBLE FRONT ENTRY DOORS DO NOT SHOW ON THE |
| | DOOR SCHEDULE NOR ARE THEY INDICATED AS EXISTING? |
| | 106.1.2* ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 5) IT ROOM INDICATES 1 HR FIRE RATED WALLS BUT THE DOOR |
| | 11JO5 IS NOT RATED? |
| | |
| | 6) SHEET A012.03 DETAIL # 2 PLEASE PROVIDE MANUFACTURES |
| | INFORMATION FOR THIS DOOR SYSTEM, DETAIL# 3 INDICATES |
| | THIS TO BE THE WALL THAT WILL TAKE THE WEIGHT OF THIS |
| | TRACK SYSTEM BUT THERE IS NO INFORMATION AS TO HOW TO |
| | ATTACH TO THE STRUCTURE ABOVE, AND WHAT TYPE OF |
| | STRUCTURE THIS SYSTEM WILL HANG FROM. WHAT IS THE |
| | WEIGHT OF THIS PAEN WALL SYSTEM PER FOOT? |
| | |
| | 7) BOTH THE CAFE AND CATERING ROOMS ARE TO COMPLY WITH |
| | : SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK |
| | |
| | 8)PLEASE PROVIDE THE MINIMUM CRITICAL RADIANT FLUX |
| | FOR THE CARPET. FBC 804.5.1 BUILDING. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |