Plan Review Notes
Plan Review Notes For Permit 07050047
Permit Number 07050047
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-26 15:34:07****************PROVISO*****************
 A) PER FBC-2004 PLUMBING, SECTION 802.2.1: THE AIR GAP
 BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL RIM
 OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE.
 B) PER FBC-2004 PLUMBING,SECTION 1002.1: A TRAP IS
 REQUIRED FOR THE HUB DRAIN WASTE PIPE.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]