| Date |
Text |
| 2007-05-16 15:11:58 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 SECTION 424, SWIMMING POOLS: |
| | ** FBC-2004 PLUMBING: |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE FOR THE SWIMMING |
| | POOL AND SPA: |
| | |
| | 1. SHEET SP-1.06: PLEASE CORRELATE THE PIPING SUPPORT |
| | DETAIL WITH THE SWIMMING POOL SCHEDULE OF EQUIPMENT. IT |
| | APPEARS THAT THE GUTTER DRAINS, WALL RETURN FITTINGS |
| | AND VACUUM FITTINGS ARE MISLABELED. PLEASE CLARIFY AND |
| | CORRECT ON THE RESUBMITTAL. |
| | |
| | 2. SHEET SP-1.07: THE POOL WASTE LINE AIR GAP DETAIL |
| | IS NOT CODE COMPLIANT PER FBC-2004 PLUMBING, SECTION |
| | 802.1.4, THE SWIMMING POOL WASTEWATER SHALL DISCHARGE |
| | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP |
| | AND PER FBC-2004 PLUMBING, SECTION 802.2.1 THE AIR GAP |
| | BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL RIM |
| | OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE THE |
| | EFFECTIVE OPENING OF THE INDIRECT WASTE. PLEASE CORRECT |
| | THIS ON THE RESUBMITTAL. |
| | |
| | 3. SHEET SP-2.01: PLEASE CORRELATE THE FILTER PIPING |
| | PLAN WITH THE SPA LINE SIZES DETAIL. IT APPEARS THAT |
| | THE PIPING IS MISLABELED AND SIZED ON THE FILTER PIPING |
| | PLAN. |
| | NOTE: THE FOLLOWING ARE MISLABELED AND SIZED WRONG ON |
| | THE FILTER PIPING PLAN. |
| | A. THE MAIN DRAIN LINE TO SPA COLLECTOR SHOULD BE |
| | LABELED AS "A", PIPE SIZING IS "OK". |
| | B. THE SUCTION LINE TO THE SPA FILTER PUMP SHOULD BE |
| | LABELED AS "D", PIPE SIZING SHOULD BE CHANGED TO |
| | 2-1/2". |
| | C. THE RETURN LINE FROM THE FILTER PUMP SHOULD BE |
| | LABELED AS "F", PIPE SIZING IS "OK". |
| | D. THE SKIMMER LINE SHOULD BE LABELED AS "C", PIPE |
| | SIZING IS OK. |
| | PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 4. SHEET SP-2.01: THE HYDRO JET PIPING PLAN IS |
| | INCORRECTLY INDICATING THE DIRECTION OF FLOW AND THE |
| | HYDRO JET PIPING SHOULD BE FROM THE THERAPY PUMPS NOT |
| | THE SPA COLLECTOR TANKS. PLEASE CLARIFY THIS ON THE |
| | RESUBMITTAL. |
| | |
| | 5. SHEET SP-2.01 SPA EQUIPMENT PIPING ISOMETRIC: |
| | PLEASE CORRELATE THE SPA EQUIPMENT ISOMETRIC WITH THE |
| | SPA EQUIPMENT SCHEDULE ON SHEET SP-2.02. IT APPEARS |
| | THAT THE FILTER, FILTER PUMP AND SPA JET PUMP ARE |
| | MISLABELED AS BEING PRESSURE GUAGES. PLEASE CORRECT |
| | THIS ON THE RESUBMITTAL. |
| | |
| | 6. SHEET SP-2.03: THE SPA WASTE LINE AIR GAP DETAIL IS |
| | NOT CODE COMPLIANT PER FBC-2004 PLUMBING, SECTION |
| | 802.1.4, THE SPA WASTEWATER SHALL DISCHARGE THROUGH AN |
| | INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP AND PER |
| | FBC-2004 PLUMBING, SECTION 802.2.1 THE AIR GAP BETWEEN |
| | THE INDRECT WASTE PIPE AND THE FLOOD LEVEL RIM OF THE |
| | WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE THE |
| | EFFECTIVE OPENING OF THE INDIRECT WASTE. |
| | PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 7. THE SUBMITTED NOTICE OF COMMENCEMENT IS EXPIRED AS |
| | OF 5/9/07, PLEASE SUBMIT A CURRENT NOTICE OF |
| | COMMENCEMENT TO BE FILED WITH THE MASTER PERMIT NUMBER |
| | 05091425. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL= [email protected] |