| 2007-05-18 13:11:39 | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES |
| | IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK |
| | AS SHOWN. |
| | PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER |
| | 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006 |
| | REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. WE |
| | ARE UNDER THE 2005 NFPA-70. (NEC) |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL AND |
| | OTHER SHEETS FROM THE BASE BUILDING WITH REVISIONS |
| | WHICH ARE NOT PART OF THE POOL OR HAVE ANY RELEVANCY TO |
| | THE SCOPE OF WORK AS APPLIED. (FIRE SPRINKLER PLANS, |
| | ELECTRICAL FOR OTHER AREAS ETC. |
| | PLEASE ONLY SUBMIT ANY PLANS WHICH ARE RELEVANT TO |
| | SCOPE OR AS REQUESTED FROM THE BASE BUILDING. MAY NOT |
| | SUBMIT REVISIONS TO BASE BUILDING UNDER POOL OR |
| | FOUNTAIN PERMITS. |
| | FBC 106.1.2 |
| | ** |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETED SIGNED, DATED AND |
| | SEALED LIGHTING PHOTO-METRICS WHICH HAVE BEEN REVIEWED |
| | AND STAMPED BY THE PALM BEACH COUNTY HEALTH DEPARTMENT |
| | FOR NIGHT-TIME SWIMMING WHICH IS BEING NOTED AND |
| | INDICATED ON PLANS. |
| | PLEASE SEE THE LIGHTING LEVELS ARE DIFFERENT FROM ONE |
| | SHEET TO SOME OF THE OTHERS WHICH REFLECT THE SAME |
| | STATEMENTS. PLEASE KNOW THE MINIMUM LEVELS ARE |
| | DETERMINED BY THE PBCHD AND PLANS ARE TO REFLECT THE |
| | MINIMUM OR ABOVE. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR AQUADYNAMICS. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES |
| | 471.023. |
| | (MISSING CERTIFICATE OF AUTHORIZATION NUMBER) |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 5) NOTE: PLEASE KNOW UPON RESEARCH FROM THE DEPARTMENT |
| | OF BUSINESS AND PROFESSIONAL REGULATION THE LICENSE FOR |
| | SAID FIRM HAS EXPIRED AND IS DELINQUENT WITH THE STATE |
| | OF FLORIDA. PLEASE SEE THE ATTACHED PRINT OUT FROM DBPR |
| | WHICH WAS PRINTED TODAY. |
| | PLEASE SEE FS 471.023 |
| | ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY THE OTHER TRADE(S). |
| | |
| | 6) NOTE: PLEASE ALSO SEE THE ATTACHED PRINT OUT FROM |
| | DBPR AS THE ADDRESSING FOR THE ENGINEER OF RECORD DOES |
| | NOT CORRELATE WITH THE STATE RECORDS FOR THE DESIGNER |
| | OF RECORD. |
| | FS 471/ FAC 61G15-23.002 |
| | |
| | 7) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS CALL |
| | FOR 925 ALABAMA, WHEN THE PROJECT ADDRESS FOR THIS |
| | BUILDING IS 550 OKEECHOBEE BLVD. |
| | PLEASE REVISE TITLE BLOCKS FOR ALL TRADES AND SHEETS. |
| | FAC 61G15-23 |
| | |
| | 8) NOTE: PLEASE BE SURE ALL SEALS FROM THE DESIGNER |
| | CONTAINS THE RAISED SEAL WHICH IS ?CLEAR AND VISIBLE* |
| | WITH ALL INFORMATION ON SAID SEAL AS REQUIRED PER FS |
| | 471.025 AND FAC 61G15-23.001. |
| | (MANY ARE VERY FAINT AND NOT READABLE) |
| | ** REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 9) NOTE: PLEASE SEE THE NOC SUBMITTED FOR BASE BUILDING |
| | HAS SINCE EXPIRED PER FS 713.13 AND 713.13(2). |
| | |
| | 10) NOTE: PLEASE SEE THE 2005 NEC FOR THE 680.26 PARTS |
| | A, B AND C AND INCLUDE THE ENTIRE NEW EQUIPOTENTIAL |
| | BONDING PLANE/GRID AS REQUIRED. (MISSING PART C). |
| | PLEASE ALSO CHECK AS THE STATE MAY BE ADJUSTING WITH A |
| | SIGNED SENATE BILL 2836 WHICH MAY PLACE INTO AFFECT THE |
| | 2008 NEC FOR SUCH AS AN IMMEDIATE CHANGE. (NOT FINAL AS |
| | OF YET). |
| | |
| | 11) NOTE: PLEASE SUBMIT A COMPLETED WIRING DIAGRAM FOR |
| | ALL ELECTRICAL EQUIPMENT SHOWING CONDUCTOR SIZES, OVER |
| | CURRENT PROTECTION, DISCONNECTS ETC. |
| | PLEASE SUBMIT LOAD CALCULATIONS ON REVISED PANEL |
| | SCHEDULE(S) WHICH ARE TO BE SUBMITTED AS THE ACTUAL |
| | KNOWN LOADS ARE NOW BEING SHOWN. THE BASE BUILDING |
| | PLANS DO NOT CONTAIN THIS INFORMATION. |
| | CONTINUOUS LOADS AT 125%. |
| | PLEASE INDICATE THE NEW OR EXISTING PANEL(S) WHICH IS |
| | FEEDING EQUIPMENT, SIZE, LOAD ETC. |
| | PLEASE KNOW AS NONE OF THIS WAS SUBMITTED, A REVIEW CAN |
| | NOT BE DONE AT THIS TIME. |
| | 215.3, 230.42, 215.5, 240.4, 310.16, 408.4, 220 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE:PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT |
| | YET SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW NOT YET MADE AS PLANS |
| | ARE NOT COMPLETE. |
| | |
| | |
| | FOUNTAIN PLANS |
| | |
| | |
| | ** UNSAT ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES |
| | IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK |
| | AS SHOWN. |
| | PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER |
| | 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006 |
| | REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. |
| | WE ARE UNDER THE 2005 NFPA-70. (NEC) |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL AND |
| | OTHER SHEETS FROM THE BASE BUILDING WITH REVISIONS |
| | WHICH ARE NOT PART OF THE POOL OR HAVE ANY RELEVANCY TO |
| | THE SCOPE OF WORK AS APPLIED. (FIRE SPRINKLER PLANS, |
| | ELECTRICAL FOR OTHER AREAS ETC. |
| | PLEASE ONLY SUBMIT ANY PLANS WHICH ARE RELEVANT TO |
| | SCOPE OR AS REQUESTED FROM THE BASE BUILDING. MAY NOT |
| | SUBMIT REVISIONS TO BASE BUILDING UNDER POOL OR |
| | FOUNTAIN PERMITS. |
| | FBC 106.1.2 |
| | ** |
| | 3 NOTE: PLEASE SEE THE ADDRESS NEEDS TO BE ON TITLE |
| | BLOCKS. THE PROJECT ADDRESS FOR THIS BUILDING IS 550 |
| | OKEECHOBEE BLVD. |
| | PLEASE REVISE TITLE BLOCKS FOR ALL TRADES AND SHEETS. |
| | FAC 61G15-23 |
| | |
| | 4) NOTE: PLEASE SUBMIT A COMPLETED WIRING DIAGRAM FOR |
| | ALL ELECTRICAL EQUIPMENT SHOWING CONDUCTOR SIZES, OVER |
| | CURRENT PROTECTION, DISCONNECTS ETC. |
| | PLEASE SUBMIT LOAD CALCULATIONS ON REVISED PANEL |
| | SCHEDULE(S) WHICH ARE TO BE SUBMITTED AS THE ACTUAL |
| | KNOWN LOADS ARE NOW BEING SHOWN. THE BASE BUILDING |
| | PLANS DO NOT CONTAIN THIS INFORMATION. |
| | CONTINUOUS LOADS AT 125%. |
| | PLEASE INDICATE THE NEW OR EXISTING PANEL(S) WHICH IS |
| | FEEDING EQUIPMENT, SIZE, LOAD ETC. |
| | PLEASE KNOW AS NONE OF THIS WAS SUBMITTED, A REVIEW CAN |
| | NOT BE DONE AT THIS TIME. |
| | 215.3, 230.42, 215.5, 240.4, 310.16, 408.4, 220 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE NOC SUBMITTED FOR BASE BUILDING |
| | HAS SINCE EXPIRED PER FS 713.13 AND 713.13(2). |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |