Plan Review Notes
Plan Review Notes For Permit 07050047
Permit Number 07050047
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-18 09:59:30BUILDING PLAN REVIEW
 PERMIT: 07050047
 ADD: 550 OKEECHOBEE BLVD
 CONT: EDWIN M. GREEN, INC
 TEL: (561)635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION. OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3)PLEASE SEE THE TITLEBLOCK FOR THE JOB LOCATION,
 PLANS INDICATE THE LOCATION TO BE 925 ALABAMA AVENUE VS
 THE PERMIT APPLICATION 550 OKEECHOBEE BLVD. PLEASE
 CORRECT THE DISCREPANCY.
  
 4) PLEASE SEE ELECTRICS COMMENTSPERTAINING TO FL
 LICESING LAWS FOR PE'S AND ALSO THEIR CERTIFICATE OF
 AUTHORIZATION.
  
 5) JUST AS ZONING, BUILDING WILL NEED TO SEE THE FULL
 FLOOR LAYOUT FOR THIS DECK, THE PLANS DOES SHOW
 STAIRWAYS, PLEASE INDICATECODE COMPLIANCE WITH
 VETICAL ACCESSIBLITY TO THE POOL AND POOL DECK, ( NOTE
 NO REQUIEMENT FOR POOL ENTRY). 11-4.1.2 ACCESSIBLE SITE
 AND EXTERIOR FACILITIES: NEW CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1,1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 6) POOL:13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 7) PLEASE SHOW COMPLIANCE WITH : 424.1.3.1.9ALL
 PUBLIC POOLS SHALL BE SURROUNDED BY A MINIMUM 48 INCH
 (1219 MM) IN HEIGHT FENCE. THE FENCE SHALL BE
 CONTINUOUS AROUND THE PERIMETER OF THE POOL AREA THAT
 IS NOT OTHERWISE BLOCKED OR OBSTRUCTED BY ADJACENT
 BUILDINGS OR STRUCTURES AND SHALL ADJOIN WITH ITSELF OR
 ABUT TO THE ADJACENT MEMBERS. ACCESS THROUGH THE
 BARRIER OTHER THAN FROM DOORED EXITS OF ADJACENT
 BUILDING(S) SHALL BE THROUGH SELF-CLOSING,
 SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM)
 MINIMAL HEIGHT WITH THE LATCH LOCATED NEAR THE TOP.
 CONSIDERATION SHALL BE GIVEN TO THE U.S. CONSUMER
 PRODUCT SAFETY COMMISSION (CPSC) PUB. NO. 362
 GUIDELINES. SAFETY COVERS THAT COMPLY WITH ASTM F 1346
 DO NOT SATISFY THIS REQUIREMENT.
  
 8) SP-1.02 PLEASE PROIDE THE FULL SCALE FLOOR PLAN
 INDICATING COMPLIANCE WITH: 424.1.6.1.2 OUTSIDE ACCESS.
 OUTSIDE ACCESS TO FACILITIES SHALL BE PROVIDED FOR
 BATHERS AT OUTDOOR POOLS. IF THEY ARE NOT VISIBLE FROM
 ANY PORTION OF THE POOL DECK, SIGNS SHALL BE POSTED
 SHOWING DIRECTIONS TO THE FACILITIES. DIRECTIONS SHALL
 BE LEGIBLE FROM ANY PORTION OF THE POOL DECK; LETTERS
 SHALL BE A MINIMUM OF 1 INCH (25 MM) HIGH.
  
 9) SP-1.05 PLEASE SEE SPACING BETWEEN DRAINS UPPER LEFT
 CORNER OF PLAN 2" DRAINS:424.1.6.5.3.1 PERIMETER
 OVERFLOW GUTTERS.
 THE LIP OF THE GUTTER SHALL BE UNIFORMLY LEVEL WITH A
 MAXIMUM TOLERANCE OF 1/4 INCH (6 MM) BETWEEN THE HIGH
 AND LOW AREAS. THE BOTTOM OF THE GUTTER SHALL BE LEVEL
 OR SLOPE TO THE DRAINS. THE SPACING BETWEEN DRAINS
 SHALL NOT EXCEED 10 FEET (3048 MM) FOR 2-INCH (51 MM)
 DRAINS OR 15 FEET (4572 MM) FOR 2?-INCH (64 MM) DRAINS,
 UNLESS HYDRAULICALLY JUSTIFIED BY THE DESIGN ENGINEER.
  
 10) SPA: ENTRAPMENT
 424.2.6.6.3 ENTRAPMENT AVOIDANCE.
 ALL POOLS AND SPAS SHALL HAVE A BACKUP SYSTEM WHICH
 SHALL PROVIDE VACUUM PROTECTION SHOULD GRATE COVERS
 BECOME MISSING OR INOPERATIVE WITH RESPECT TO THEIR
 APPROVED USE. VACUUM PROTECTION DEVICES SHALL CONSIST
 OF ONE OF THE FOLLOWING:
 1.APPROVED SAFETY VACUUM RELEASE SYSTEM (SVRS).
 2.APPROVED VENT PIPING.
 3.OTHER APPROVED DEVICES OR MEANS.
  
 11) SPA HEATER;13-412.1.ABC.2.6.2 POOL COVERS. HEATED
 POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT POOL
 COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO MORE
 THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A MINIMUM
 INSULATION VALUE OF R -12. EXCEPTION: POOLS DERIVING
 OVER 60 PERCENT OF THE ENERGY FOR HEATING FROM
 SITE-RECOVERED ENERGY OR SOLAR ENERGY SOURCE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  