Date Text
2007-05-09 07:46:58 
  
 NOTE:
  
 680.26(B)(5) ----AND ALL FIXED METAL PARTS EXCEPT THOSE
 SEPARATED FROM THE POOL BY A PERMANENT BARRIER SHALL BE
 BONDED THAT ARE WITHIN THE FOLLOWING DISTANCES OF THE
 POOL:
 EXAMPLES OF FIXED METAL PARTS BOUND BY THIS REQUIREMENT
 INCLUDE METAL FENCES, METAL AWNINGS, METAL DOOR FRAMES,
 AND METAL WINDOW FRAMES.
 (1) WITHIN 1.5 M (5 FT) HORIZONTALLY OF THE INSIDE
 WALLS OF THE POOL
 (2) WITHIN 3.7 M (12 FT) MEASURED VERTICALLY ABOVE THE
 MAXIMUM WATER LEVEL OF THE POOL, OR ANY OBSERVATION
 STANDS, TOWERS, OR PLATFORMS, OR ANY DIVING
 STRUCTURES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718