Plan Review Notes
Plan Review Notes For Permit 07050038
Permit Number 07050038
Review Stop G
Sequence Number 1
Notes
Date Text
2007-05-24 14:23:44DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. ONE OF THE SUBMITTED SURVEYS OF THE PROPOSED WORK
 IS IN PENCIL. PLANS SUBMITTED IN PENCIL ARE
 UNACCEPTABLE. PLEASE CORRECT.
  
 2.A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 3. PLEASE SUBMIT MANUFACTRER SPECIFICATIONS OF
 PROPOSED 2 PSI TO 0.5 PSI MP REGULATORS INDICATING THE
 MANUFACTURER'S NAME, MODEL NUMBER, MAXIMUM LOAD
 CAPACITY AND SHOW A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL).
  
 4. NOTE: A MP REGULATOR IS REQUIRED AND MUST BE
 INSTALLED FOR THE PROPOSED FUTURE BBQ. PLEASE INDICATE
 THE REGULATOR ON THE RESUBMITTAL.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721