| 2007-05-24 14:23:44 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. ONE OF THE SUBMITTED SURVEYS OF THE PROPOSED WORK |
| | IS IN PENCIL. PLANS SUBMITTED IN PENCIL ARE |
| | UNACCEPTABLE. PLEASE CORRECT. |
| | |
| | 2.A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR |
| | THE GENERATOR LOCATION. |
| | |
| | 3. PLEASE SUBMIT MANUFACTRER SPECIFICATIONS OF |
| | PROPOSED 2 PSI TO 0.5 PSI MP REGULATORS INDICATING THE |
| | MANUFACTURER'S NAME, MODEL NUMBER, MAXIMUM LOAD |
| | CAPACITY AND SHOW A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY (NRTL). |
| | |
| | 4. NOTE: A MP REGULATOR IS REQUIRED AND MUST BE |
| | INSTALLED FOR THE PROPOSED FUTURE BBQ. PLEASE INDICATE |
| | THE REGULATOR ON THE RESUBMITTAL. |
| | |
| | 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |