| Plan Review Notes For Permit 07050038 |
| Permit Number |
07050038 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-21 10:51:22 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | 2} INDICATE ON THE PANEL SCHEDULE (GENERATOR CALC'S) | | | SHEET'S, THAT IT IS THE SCHEDULE FOR THE TRANSFER | | | SWITCH. | | | | | | 3} INDICATE CONDUIT SIZE AND TYPE, AND NUMBER OF | | | CONDUCTORS FOR THE RUN TO THE TRANSFER SWITCH FROM THE | | | EXISTING PANEL. | | | | | | NOTE: 702.8 A SIGN SHALL BE PLACED AT THE | | | SERVICE-ENTRANCE EQUIPMENT THAT INDICATES THE TYPE AND | | | LOCATION OF ON-SITE OPTIONAL STANDBY POWER SOURCES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|