2007-05-17 08:54:03** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN
 EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS
 SHOWN.
 PLEASE SEE THE PLANS CALL FOR A 2006 FBC WHICH AT THIS
 TIME, THERE IS NO 2006. PLEASE KNOW HOWEVER AT THIS
 TIME AND AS OF DECEMBER 8TH, 2006 THE STATE IS UNDER
 THE 2004 FBC W/2006 REVISIONS. THESE ARE ONLY REVISIONS
 TO THE 2004 FBC.
 PLEASE ALSO SEE THE PLANS INDICATE THE 2002 NEC WHICH
 WENT OUT FOR ALL PERMIT APPLICATIONS AFTER THIS SAME
 DATE. WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY REQUEST TO SHOW HOW EQUIPMENT WILL BE
 INTERFACED WITH ANY EXISTING FIRE ALARM SYSTEM(S).
 PLEASE SEE NEC AND LS CODE WHICH REQUIRES
 DISCONNECTS/SHUNT OF EQUIPMENT IN EVENTS.
 PLEASE SEE 620.51, NFPA-72, ASME A-17.1-2004
  
 3) NOTE: PLEASE SEE PLANS MENTIONS WORK FOR ELEVATOR
 EQUIPMENT BY STATE, HOWEVER MANY OF THE ITEMS WHICH ARE
 NOT COVERED BY THE STATE AND IS PERMITTED BY THE
 ELECTRICAL CONTRACTOR AND THE LOCAL AHJ IS NOT SHOWN.
 PLEASE COMPLETE INFORMATION ON MOTORS/EQUIPMENT LOADS
 BEING INSTALLED.
 PLEASE SEE620.22 AS INFORMATION FOR THESE CIRCUITS
 COULD NOT BE LOCATED.
 PLEASE SEE THE SAME SECTIONS AND INDICATE THE
 FT-CANDLES AS REQUIRED.
 PLANS CALL FOR A 100AMP DISCONNECT FOR THE EQUIPMENT,
 HOWEVER NO INFORMATION WAS SHOWNON ELECTRICAL RISER,
 PANELS ETC FOR THIS.?
 PLEASE COMPLETE.
 215.5, 240.4, 310.16, ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE 700.16,700.12, LS 101 7.8 AND 7.9
 AS AN EMERGENCY BATTERY BACK UP LIGHT OF SOME KIND WILL
 BE REQUIRED FOR THIS ROOM.
  
 5) NOTE: PLEASE SEE13-415.1.ABC.1.1, .1.2 AS LIGHTING
 CONTROL IS REQUIRED FOR ANY NEW INSTALLATIONS OF
 LIGHTING CONTROL.
  
 6) NOTE: PLEASE CLARIFY CIRCUITING ON PLANS FOR A/C
 SYSTEM AS SHOWN ON PANEL SCHEDULE.
 PLEASE ALSO SEE THAT BOTH UNITS DO NOT INDICATE ANY
 DISCONNECTS AS REQUIRED PER 440.11
 PLEASE SEE NO SERVICE GFI SHOWN FOR CU. 210.63, 210.8
  
 7) NOTE: PLEASE SEE THE VLAUE SHALL INCLUDE ALL LABOR,
 MATERIALS AND EQUIPMENT, EVNE IF ANY IS OWNER SUPPLIED.
 FBC 108.3
  
 ** PLEASE KNOW THAT AS SOME INFORMATION WAS NOT
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]