| 2007-05-17 08:54:03 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN |
| | EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS |
| | SHOWN. |
| | PLEASE SEE THE PLANS CALL FOR A 2006 FBC WHICH AT THIS |
| | TIME, THERE IS NO 2006. PLEASE KNOW HOWEVER AT THIS |
| | TIME AND AS OF DECEMBER 8TH, 2006 THE STATE IS UNDER |
| | THE 2004 FBC W/2006 REVISIONS. THESE ARE ONLY REVISIONS |
| | TO THE 2004 FBC. |
| | PLEASE ALSO SEE THE PLANS INDICATE THE 2002 NEC WHICH |
| | WENT OUT FOR ALL PERMIT APPLICATIONS AFTER THIS SAME |
| | DATE. WE ARE UNDER THE 2005 NFPA-70. (NEC). |
| | PLEASE ALSO LIST THE FOLLOWING. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY REQUEST TO SHOW HOW EQUIPMENT WILL BE |
| | INTERFACED WITH ANY EXISTING FIRE ALARM SYSTEM(S). |
| | PLEASE SEE NEC AND LS CODE WHICH REQUIRES |
| | DISCONNECTS/SHUNT OF EQUIPMENT IN EVENTS. |
| | PLEASE SEE 620.51, NFPA-72, ASME A-17.1-2004 |
| | |
| | 3) NOTE: PLEASE SEE PLANS MENTIONS WORK FOR ELEVATOR |
| | EQUIPMENT BY STATE, HOWEVER MANY OF THE ITEMS WHICH ARE |
| | NOT COVERED BY THE STATE AND IS PERMITTED BY THE |
| | ELECTRICAL CONTRACTOR AND THE LOCAL AHJ IS NOT SHOWN. |
| | PLEASE COMPLETE INFORMATION ON MOTORS/EQUIPMENT LOADS |
| | BEING INSTALLED. |
| | PLEASE SEE620.22 AS INFORMATION FOR THESE CIRCUITS |
| | COULD NOT BE LOCATED. |
| | PLEASE SEE THE SAME SECTIONS AND INDICATE THE |
| | FT-CANDLES AS REQUIRED. |
| | PLANS CALL FOR A 100AMP DISCONNECT FOR THE EQUIPMENT, |
| | HOWEVER NO INFORMATION WAS SHOWNON ELECTRICAL RISER, |
| | PANELS ETC FOR THIS.? |
| | PLEASE COMPLETE. |
| | 215.5, 240.4, 310.16, ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE SEE 700.16,700.12, LS 101 7.8 AND 7.9 |
| | AS AN EMERGENCY BATTERY BACK UP LIGHT OF SOME KIND WILL |
| | BE REQUIRED FOR THIS ROOM. |
| | |
| | 5) NOTE: PLEASE SEE13-415.1.ABC.1.1, .1.2 AS LIGHTING |
| | CONTROL IS REQUIRED FOR ANY NEW INSTALLATIONS OF |
| | LIGHTING CONTROL. |
| | |
| | 6) NOTE: PLEASE CLARIFY CIRCUITING ON PLANS FOR A/C |
| | SYSTEM AS SHOWN ON PANEL SCHEDULE. |
| | PLEASE ALSO SEE THAT BOTH UNITS DO NOT INDICATE ANY |
| | DISCONNECTS AS REQUIRED PER 440.11 |
| | PLEASE SEE NO SERVICE GFI SHOWN FOR CU. 210.63, 210.8 |
| | |
| | 7) NOTE: PLEASE SEE THE VLAUE SHALL INCLUDE ALL LABOR, |
| | MATERIALS AND EQUIPMENT, EVNE IF ANY IS OWNER SUPPLIED. |
| | FBC 108.3 |
| | |
| | ** PLEASE KNOW THAT AS SOME INFORMATION WAS NOT |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW FOR CODE COMPLIANCE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |