| 2007-06-15 17:47:48 | BUILDING PLAN REVIEW |
| | PERMIT: 07050024 |
| | ADD: 208 CLEMATIS ST |
| | CONT: FINLEY CONSTRUCTION |
| | TEL: (561) 352-5856 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3A) PLANS INDICATE THAT THEY ARE DESIGNED TO THE 2006 |
| | FBC PLEASE CORRECT TO THE 2004 FBC WITH 2006 AMENMENTS. |
| | ALSO INCLUDE THE 2004 FBC EXISTING BUILDING CODE WITH |
| | 2006 AMENDMENTS. PROVIDE WHAT LEVEL OF ALTERATION IS |
| | BEING COMPLETED UNDER THIS PERMIT. |
| | |
| | 3B) PLEASE SEE EXISTING BUILDING TYPE INDICATES A V, |
| | SPRINKLERED TABLE 503 WILL NOT ALLOW MERCANTILE NOR R2 |
| | SIX FLOORS HIGH, PLEASE REVIEW TABLE 503 FOR MERCANTILE |
| | AND R2 RESIDENCE FORTHE MINIMUM BUILDING TYPE! |
| | |
| | 4) PLEASE PROVIDE WIND DESIGN INFORMATION: 2004 FL. |
| | BLD CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED TO |
| | WIND SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | A)EXTERIOR FIRE RATED DOOR |
| | B) WALL LOUVER |
| | C) NEW PRE MANUFACTURED A/C STAND |
| | |
| | 6)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 7) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |