| 2007-05-07 14:47:53 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PER FBC-2004, CHAPTER 1, SECTION |
| | 106.1.3, QUALITY OF BUILDING PLANS: THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, STANDARDS FOR PLANS |
| | AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, |
| | CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | NOTE: PLEASE CLEARLY INDICATE THE POOL HEATERS LOCATION |
| | ON THE RESUBMITTED DRAWINGS. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: PLEASE INDICATE THE CORRESPONDING LENGTHS OF THE |
| | CUT SECTIONS OF PIPE ON THE RESUBMITTAL TO VERIFY THE |
| | LONGEST LENGTH OF THE SYSTEM. |
| | |
| | 3. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON |
| | THE RESUBMITTED DRAWINGS. |
| | |
| | 4. PLEASE SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, SHOWING LISTINGS FROM A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), BTU |
| | LOAD, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | A} MP REGULATORS |
| | B} GAS RANGE |
| | C} DRYER |
| | D}WATER HEATER |
| | |
| | 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE INDICATE |
| | THE SHUTOFF VALVE ON THE RESUBMITTAL. |
| | |
| | 6. PER FBC-2004 FUEL GAS, SECTION 404.13.3AN |
| | INSULATED COPPER TRACER WIRE SHALL BE INSTALLED |
| | ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE |
| | TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE |
| | INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| | PLEASE INDICATE THE TRACER WIRE ON THE RESUBMITTAL. |
| | |
| | 7. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |