2007-05-14 10:37:44*****DENIED*****
  
  
  
 IN REFERENCE TO THE HYDRAULIC SUMMARY LISTED ON PAGE
 TWO OF THE REPORT DESCRIPTION SHEETS, THE SAFETY MARGIN
 OF 4.083 PSI IS UNACCEPTABLE.AS PER WEST PALM BEACH
 FIRE PREVENTION, A SAFETY MARGIN OF AT LEAST 5.0 PSI IS
 REQUIRED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW