| Plan Review Notes For Permit 07040996 |
| Permit Number |
07040996 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-19 21:05:55 | | | | | | | DENIED | | | | | | 1)THE DESIGN PRESSURE FOR WINDOW #6-33.0 PSF DOES | | | NOT MEET THE REQUIRE PRESSURE FOR THAT OPENING -35.9 | | | PSF PER YOUR DESIGN PRESSURE SHEET | | | | | | 2)THE STORM PANEL SCHEDULE HAS C5 CONNECTION TYPE BUT | | | DRAWING SHOWS C1 AND C4 CIRCLED, PLEASE CLARIFY WHAT | | | WILL BE USED, ALSO IF FLOOR MOUNT IS USED IS IT INTO | | | WOOD OR CONCRETE? | | | | | | 3)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO A PERMIT BEING | | | ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|