| 2007-07-18 13:22:47 | --------------DENIED------------------ |
| | |
| | FBC 2004 CODE FAMILY W/ 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | NFPA 664-02 |
| | |
| | 1.NOTE ON PLANS IN TITLE BLOCK STILL INDICATES THAT THE |
| | ENGINEER IS ONLY TAKING RESPONSIBILITY FOR THE |
| | STRUCTURAL ELEMENTS OF THIS PLAN. PLEASE CORRECT AND |
| | RESUBMIT. |
| | |
| | 2. ENGINEER'S ADDRESS AS SHOWN ON PLANS DOES NOT MATCH |
| | THE ADDRESS SHOWN IN DBPR'S RECORDS. PLEASE SEE FAC |
| | RULE 61G15-23.002(2). PLEASE CORRECT THE ADDRESS ON |
| | PLANS OR UPDATE LICENSE INFORMATION WITH DBPR. |
| | |
| | 3. CODES AS STATED ON PAGE 4 OF PLANS: NFPA 91 IS |
| | LISTED. HOWEVER, NFPA 91 IS THE STANDARD FOR EXHAUST |
| | AND CONVEYANCE OF NON COMBUSTIBLE PARTICULATE SOLIDS. |
| | THE CORECT STANDARD IS NFPA 654 FOR THE HANDLING OF |
| | COMBUSTIBLE PARTICULATE SOLIDS. SEE NFPA 664-02 SEC |
| | 8.2.2.1.1. |
| | |
| | 4. AN IMPORTANT PART OF THE "FLAMEX" SYSTEM |
| | DOCUMENTATION WAS NOT PROVIDED, SUCH AS PART V COVERING |
| | THE LOCATION OF COMPONENTS FOR INSTALLATION. PLEASE |
| | PROVIDE ALL RELEVANT INFORMATION TO FACILITATE A |
| | COMPLETE REVIEW OF PLANS. FBC 106.1.2 |
| | |
| | 5. PLEASE PROVIDE "DUCT INC." SUBMITTAL DATA WITH |
| | INSTRUCTIONS. THE HANGER SPACING AS SHOWN ON PLANS IS |
| | GREATER THAT WHAT IS CALLED FOR IN SMACNA DUCT |
| | CONSTRUCTION STANDARDS. ALSO, PLEASE PROVIDE HANGING |
| | DETAIL SHOWIN HOW DUCT IS TO BE SUPPORTED FROM THE |
| | BUILDING STRUCTURE. |
| | |
| | 6. PG 5 STATES "MINIMUM SENSOR-TO-VALVE DISTANCE IS 20' |
| | BASED ON A MAXIMUM AIR VELOCITY OF 4,000 FPM." HOWEVER, |
| | 24" ROUND DUCT CARRYING 13,000 CFM HAS A VELOCITY OF |
| | 4,140 CFM. PLEASE SEE COMMENT 4 REGARDING MISSING |
| | INFORMATION NEEDED TO DETERMINE PROPER SENSOR-TO-VALVE |
| | DISTANCE. |
| | |