Date Text
2007-07-24 16:38:17 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE THE LISTING AGENCY AND LISTING NUMBER FOR
 THE DUST COLLECTOR AND THE FLAMEX DETECTION SYSTEM.
  
 2} INDICATE THE PURPOSE OF THE TWO 1HP 3PHASE MOTORS
 SHOWN BEING FED FROM THE DUST COLLECTER CONTROL PANEL
 ON SHEET E-1
  
 3}THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK,
 SHEET E-1, SHALL INDICATE THE CERTIFICATE OF
 AUTHORIZATIONNUMBER ALONG WITH OTHER INFORMATION
 REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE.
  
 4} SEE MECHANICAL REVIEW FORCOMMENTS REGARDING THE
 ENGINEERS ADDRESS AND STATEMENT "STRUCTURAL PROVISIONS"
 IN THE TITLE BLOCK, SHEET 5.(FLAMEX FIRE SYSTEM).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  