2007-08-15 11:50:58BUILDING PLAN REVIEW
 PERMIT: 07040994
 ADD: 4300 NFLAGLER DR
 CONT: MECHANICAL INDUSTRIAL SERVICES
 TEL: (813)247-2868
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATETHE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OF COMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) 2ND REQUEST,DIGITAL DESIGN AND DRAFTING IS ACTING
 AS AN ENGINEER AND ARE NOT CERTIFIED OR LICENSED AS AN
 ENGINEER OR ENGINEERING BUSINESS IN ACCORDANCE WITH
 CHAPTER 471,
 FLORIDA STATUTE. PLEASE SEE DBPR CASENO. 03-0489. IT
 APPEARS THAT DIGITAL DESIGN IS PRACTICING ENGINEERING,
 IF THE FIRM WERE DIRECTLY ENGAGED BY THE ENGINEER THEY
 WOULD NOT NEED TO HAVE THEIR NAME ON THE HEADER STRIP,
 IT APPEARS THAT THEY ARE ADVERTISING THEMSELVES AS
 ENGINEERS. THIS WILL BE TURNED OVER TO THE STATE TO
 INVESTIGATE AS PER CONVERSATION WITH STATE INVESTIGATOR
 MR. JACK BEMESS.
  
 5) 2ND REQUEST,LS & SS SERVIDES INC,IS ACTING AS AN
 ENGINEER AND ARE NOT CERTIFIED OR LICENSED AS AN
 ENGINEER OR ENGINEERING BUSINESS IN ACCORDANCE WITH
 CHAPTER 471,FLORIDA STATUTE. PLEASE SEE DBPR NO
 03-0489 . ALL RESPONSE SHEET COMMENTS DO NOT INDICATE
 THAT THEY ARE THE DESIGN ENGIEENERS BUT LYLE
 SCHARENBURG OF LS & SS SERVICES INC. BOTH THE
 MECHANICAL AND BUILDING REVIEWER HAVE HAD
 MULTIPLE TELEPHONE CALLS WITH MR SCHARENBURG WHERE HE
 IMPLIED THAT THIS IS HIS DESIGN AND SEALED BY ENGINEER
 J. F. SHANNON. THE RESPONSE TO BUILDINGS COMMENT NUMBER
 (5
 ) DOESN'T INDICATE THE PLANS WERE DESIGNED BUT SEALED
 BY THE ENGINEER OF RECORD.
  
 6A)SEMI- COMPLIED, 106.1.2 ADDITIONAL INFORMATION IS
 REQUIRED TO BE ABLE TO DO AN ADEQUATE REVIEW,PLEASE
 PROVIDE:110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 6B) THE DESIGN PROFESSIONAL HAS NOT COMMENTED ON THIS
 ISSUE, AGAIN LYLE SCHARENBERG OF LS & SS SERVES INC
 MAKES THE REBUTTAL NOT THE DESIGNER OF RECORD!!!!! THE
 REMAINDER OF THE REVIEW WILL USE THE FOLLOWING
 ASSUMPTIONS:
 NOTE: THIS REVIEW WILL BE COMPLETED WITH THE FOLLOWING
 ASSUMPTION, THE WOOD WORKING SHOP WILL BE CONSIDERED
 FACTORY-INDUSTRIAL F1 SINCE SECTION 306 OF THE BUILDING
 CODE DOES LIST MILLWORK (SASH & DOOR) AS AN F1
 OCCUPANCY.
  
 THE NEXT ISSUE WILL BE HOW TO CLASSIFY THE SAWDUSST
 THAT IS CREATED WHEN WORK IS BEING COMPLETED. THE WOOD
 BEFORE IT IS CUT IS A MINOR HAZARD BUT WHEN SAWDUST IS
 CREATED, THE SAWDUST IS VERY COMBUSTIBLE AND CREATES A
 HIGH HAZARD OR H-2 OCCUPANCY. TABLE 307.7(1)IS FOR
 THE MAXIMUM ALLOWABLE QUANITIES OF MATERIAL ALLOWED PER
 CONTROL AREA, THAT POSES A PHYSICAL HAZARD. WHEN YOU
 SCAN THE TABLE THERE IS NO CATEGORY FOR COMBUSTIBLE
 DUST, THERE IS FOR COMBUSTIBLE FIBERS NOT COMBUSTIBLE
 DUST! PLACING THE COMBUSTIBLE DUST INTO A H-2 CATEGORY.
 SEE 415.7 GROUP H-2
  
 415.7.1 COMBUSTIBLE DUSTS, GRAIN PROCESSING AND
 STORAGE.
 THE PROVISIONS OF SECTIONS 415.7.1.1 THROUGH 415.7.1.5
 SHALL APPLY TO BUILDINGS IN WHICH MATERIALS THAT
 PRODUCE COMBUSTIBLE DUSTS ARE STORED OR HANDLED.
 BUILDINGS THAT STORE OR HANDLE COMBUSTIBLE DUSTS SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF NFPA 61, NFPA
 120, NFPA 651, NFPA 654, NFPA 655, NFPA 664 AND NFPA
 85, AND THE FLORIDA FIRE PREVENTION CODE.
  
 WHEN YOU LOOK AT THE VARIOUS NFPA REQUIREMENTS ABOVE
 664 IS THE STANDARD TO BE USED . NFPA 664 IS THE
 STANDARDFOR THE PREVENTION OF FIRE AND EXPLOSIONS IN
 WOOD PROCESSING FACILITIES 2007 EDITION. WE BELIEVE
 THAT THIS STILL CAN BE CLASSIFIED AS A F-1 FACTORY USE
 WITH ONE CONTROLED AREA THE WOOD SHOP AND THE DUST
 COLLECTION SYSTEM HAS TO TIED INTO
 OPERATION OF ANY EQUIPMENT THAT CREATES SAWDUST. THIS
 WOULDMAKE THE COLLECTION SYSTEM AND HOLDING TANK THE
 H-2 HAZARD ZONE.
  
 IN STUDYING 415.7.1 THE NFPA WHICH REFERS TO WOOD AND
 OR COMBUSTIBLE SAWDUST IS NFPA 664 AND IS TO BE
 FOLLOWED COMPLETELY.
 4.4 DESIGNER AND INSTALLER QUALIFICATIONS. SYSTEMS THAT
 HANDLE COMBUSTIBLE PARTICLES SHALL BE DESIGNED BY AND
 INSTALLED UNDER THE SUPERVISION OF QUALIFIED ENGINEERS
 WHO ARE KNOWLEGABLE OF THESE SYSTEMS AND THEIR
 ASSOCIATED HAZARDS. PLEASE NOTE THAT THE ENGINEER OF
 RECORD STATES HE HAS DESIGNED THE STRUCTURE
 STRUCTURALLY TO THE 2004 FBC NOT THE MECHANICAL
 ASSPECTS OF THE SYSTEM.
 ATTACHED IS A COPY OF NFPA 664 TO FOLLOW IN THE DESIGN
 OF THE SYSTEM PLEASE COMPLY WITH ALL SECTION OF THIS
 STANDARD, INCLUSIVE OF CHAPTER 12.
  
 PLEASE PROVIDE INFORMATION ON THE BULK STORAGE TANK
 SIZE IN WIDTH DEPTH AND HEIGTH AS WELL AS CU FT
  
 PROVIDE THE EMPLOYEE TRAINING PROGRAM IN SECTION IN
 11.1 AND 11.3.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  