| Plan Review Notes For Permit 07040994 |
| Permit Number |
07040994 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-03 14:29:28 | ----------------DENIED---------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | NFPA 966 | | | | | | | | | 1. THIS PLAN HAS BEEN SIGNED/SEALED BY AN ENGINEER FOR | | | STRUCTURAL ELEMENTS ONLY. WHO IS THE DESIGN | | | PROFESSIONSAL RESPONSIBLE FOR THE DUST COLLECTION | | | SYSTEM? DIGITAL DESIGN AND DRAFTING MAY NOT OFFER | | | ENGINEERING SERVICES PER F.S. 471.003. PLEASE RESUBMIT | | | DRAWINGS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER | | | TAKING RESPONSIBILITY FOR THE DESIGN OF THE DUST | | | COLLECTION SYSTEM. | | | | | | 2. THE USAGE OF THIS PORTION OF THE BUILDING AS A | | | WOODWORKING FACILITY REQUIRES CONFORMANCE WITH NFPA 664 | | | IN ACCORDANCE WITH FBC,M 511.4. | | | | | | 3. BUILDING, FIRE, ELECTRICAL AND ZONING REVIEWS ARE | | | ALSO REQUIRED. A CHANGE OF USAGE CLASS FOR THIS PORTION | | | OF THE BUILDING MAY BE REQUIRED PENDING THESE OTHER | | | REVIEWS. | | | | | | 4. THE INSTALLATION AND APPROVAL OF THE DUST COLLECTION | | | SYSTEM WILL BE REQUIRED FOR CODE COMPLIANCE PRIOR TO | | | ISSUANCE OF A C.O. FBC,M 510.2.1. A COMPLETE REVIEW OF | | | THE DUST COLLECTION SYSTEM WILL BE PERFORMED ONCE THE | | | REQUIREMENTS OF COMMENT #1 HAVE BEEN MET. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|