Plan Review Notes
Plan Review Notes For Permit 07040976
Permit Number 07040976
Review Stop M
Sequence Number 1
Notes
Date Text
2007-05-03 09:10:28*** DENIED ***
 1) MECHANICAL PLANS SHOW EXISTING OPEN OFFICE #803 HAS
 1,200 CFM'S. OF SUPPLY AIR AND ONLY 600 CFM'S. OF
 RETURN AIR, SEE 2004 FBC/M 601.4 BALANCED RETURN AIR,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.