| Plan Review Notes For Permit 07040976 |
| Permit Number |
07040976 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-03 09:10:28 | *** DENIED *** | | | 1) MECHANICAL PLANS SHOW EXISTING OPEN OFFICE #803 HAS | | | 1,200 CFM'S. OF SUPPLY AIR AND ONLY 600 CFM'S. OF | | | RETURN AIR, SEE 2004 FBC/M 601.4 BALANCED RETURN AIR, | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|