2007-05-14 12:16:13*****DENIED*****
  
  
 1.THE COMPLETE/CORRECT ADDRESS OF WHERE THE SCOPE OF
 WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.EXPLAIN THE DIFFERENCE
 BETWEEN SUITE 201 AND THAT OF 2-A-A.
  
 2.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.PLEASE BE ADVISED THAT INTERIOR WALL AND CEILING
 FINISH MATERIAL SHALL BE CLASS A OR CLASS B IN EXITS
 AND IN EXIT ACCESS CORRIDORS.CLASS C IS INDICATED ON
 SHEET A500.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW