| Notes |
| Date |
Text |
| 2007-05-14 12:16:13 | *****DENIED***** | | | | | | | | | 1.THE COMPLETE/CORRECT ADDRESS OF WHERE THE SCOPE OF | | | WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF | | | EACH SUBMITTED PLAN SHEET.EXPLAIN THE DIFFERENCE | | | BETWEEN SUITE 201 AND THAT OF 2-A-A. | | | | | | 2.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE - | | | SHALL BE REFERENCED. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.PLEASE BE ADVISED THAT INTERIOR WALL AND CEILING | | | FINISH MATERIAL SHALL BE CLASS A OR CLASS B IN EXITS | | | AND IN EXIT ACCESS CORRIDORS.CLASS C IS INDICATED ON | | | SHEET A500. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|