Plan Review Notes
Plan Review Notes For Permit 07040951
Permit Number 07040951
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-30 11:59:59*** DENIED ***
 1) UNABLE TO DO A COMPLETE PLAN REVIEW AT THIS TIME, AS
 THE MECHANICAL PLANS FLOOR LAYOUT DOES NOT MATCH THE
 BUILDING PLANS ON FILE, PLEASE REVISE BUILDING PLANS.
  
 2) BUILDING PLANS ON FILE SHOW NO INSULATION ON ANY
 WALLS IF AIR CONDITIONING IS TO BE ADDED PLEASE REVISE
 BUILDING PLANS.
  
 3) BUILDING PLANS ON FILE SHOW TWO GAS WATER HEATERS IN
 THE MECHANICAL ROOM IF A DOOR IS AT THE MECHANICAL ROOM
 THEN THIS SPACE MAY BE A CONFINED SPACE, PLEASE PROVIDE
 COMBUSTION AIR CALCULATIONS, AND IF NEEDED PROVIDE
 COMBUSTION AIR, SEE 2004 FBC/R M1701.
  
 4) IF NO DOOR TO THE MECHANICAL ROOM THEN THE ENTIRE
 GARAGE NEEDS TO BE INSULATED, SEE 2004 FBC CHAPTER 13,
 REVISE BUILDING PLANS.
  
 5) BUILDING PLANS ON FILE SHOW A GAS CLOTHES DRYER IN
 THE LAUNDRY ROOM, PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS, IF NEEDED PROVIDE COMBUSTION AIR, SEE
 2004 FBC/R M1701.
  
 6) BUILDING PLANS ON FILE SHOW NO DOOR TO THE ROOM NEXT
 TO THE LAUNDRY ROOM IF NO DOOR TO THE GARAGE SEE NOTE
 #4 ABOVE.
  
 7) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 9) SEE 2004 FBC/R M1602.2 (4) RETURN AIR PROHIBITED
 SOURCES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.