| 2008-07-08 15:17:35 | ** DENIEDREVISIONS ** |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS WHICH ARE SHOWN ON PLANS DO NOT MATCH WITH |
| | PLANS. |
| | PLEASE SEE THE FIXTURE LEGEND NEEDS TO BE COMPLETED. |
| | SOME EXAMPLES OF THIS WOULD BE THE TRACK LIGHTING WHICH |
| | IS MISSING FROM THE FIXTURE LEGEND.THIS IS ONE |
| | EXAMPLE OF FIXTURES ON PLANS NOT ON LEGEND AND IN |
| | CALCULATIONS. |
| | PLANS INDICATE A 60W FLUORESCENT FIXTURE/BULB. PLEASE |
| | VERIFY. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED AS METHOD |
| | *A* MAY NOT BE SUED. PLEASE SEE 13-101.1.0. HOW CAN |
| | METHOD *A* BE USED? |
| | PLEASE SEE 13-400.3.B, 13-400.3.A AND 13-400.3.C. THE |
| | VERSIONS OF CALCULATIONS SUBMITTED AS 3.0 MAY NOT BE |
| | USED. THE CURRENT VERSION FOR PERMIT APPLICATIONS IS |
| | 2.5. |
| | PLEASE KNOW IN ANY CASE THE LIGHTING AS SHOWN IN THE |
| | INPUT DATA REPORT DOES NOT COORDINATE WITH PLANS. |
| | PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE BE SURE TO SEE THAT ALL FIXTURE WATTAGES ARE |
| | USED AND NOT BULB WATTAGE. PLEASE REVISE THE |
| | CALCULATIONS AND BE SURE TO SEE THE SPECIFIC |
| | REQUIREMENTS OF TRACK LIGHTING. |
| | |
| | 2) NOTE: PLEASE VERIFY NEW TENANT SPACE WITH TWO |
| | SEPARATE METERS AND MAINS. |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | NEC |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |