| 2008-07-01 10:01:47 | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. SHEET P-2.1 NATURAL GAS RISER DIAGRAM: |
| | SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | NOTE: THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING |
| | THE CORRESPONG LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | REFERENCE THE RED CIRCLED YELLOW HIGH LIGTHED AREAS |
| | INDICATING THIS AND COMPLY. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: REFERENCE COMMENT #1 AND CORRELATE THE "GAS |
| | SIZING BASED ON THE FOLLOWING" TABLE TO REFLECT THE |
| | CORRECT "MAXIMUM DEVELOPED LENGTH". THE ADDED SUM FROM |
| | THE METER TO THE FARTHEST APPLIANCE IS 101'. THE PLANS |
| | ARE INDICATING 98' WHICH IS INCORRECT. UNTIL COMMENT #1 |
| | IS ADDRESSED AND PLANS CORRELATED GAS WILL CONTINUE TO |
| | FAIL PLAN REVIEW. THE UNDERGROUND PE PIPING TO THE |
| | GENERATOR IS UNDERSIZED. THE FBC- FUEL GAS TABLE |
| | 402.4(20) FOR 1-1/2" PE @ 125' IS ONLY GOOD FOR 550,000 |
| | BTU'S, HOWEVER THE PLANS ARE INDICATING A BTU LOAD |
| | CAPACITY FOR THE GENERATOR AS BEING 1,012,000 BTU'S. |
| | THE FBC- FUEL GAS TABLE 402.4(20) @ 125' ONLY GOES UP |
| | TO 2" PIPE WHICH IS ONLY GOOD FOR 871,000 BTU'S. PLEASE |
| | REFERENCE THE ATTACHED GAS TABLES INDICATING THIS. |
| | PLEASE PROVIDE A SIZING TABLE INDICATING COMPLIANCE OR |
| | CHANGE SYSTEM TO A 2 PSI DELIVERY PRESSURE. |
| | |
| | 3. SHEET P-1.1 AND P-2.1 PLEASE CORRELATE GENERATOR |
| | WITH ELECTRICAL SHEETS E-21 AND E-3.1 AND INDICATE THE |
| | GENERATOR A "FUTURE" APPLIANCE. NOTE: GENERATOR IS |
| | UNDER A SEPERATE PERMIT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |