2008-07-01 10:01:47GAS PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET P-2.1 NATURAL GAS RISER DIAGRAM:
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING
 THE CORRESPONG LENGTHS TO ALL CUT SECTIONS OF PIPE.
 REFERENCE THE RED CIRCLED YELLOW HIGH LIGTHED AREAS
 INDICATING THIS AND COMPLY.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1 AND CORRELATE THE "GAS
 SIZING BASED ON THE FOLLOWING" TABLE TO REFLECT THE
 CORRECT "MAXIMUM DEVELOPED LENGTH". THE ADDED SUM FROM
 THE METER TO THE FARTHEST APPLIANCE IS 101'. THE PLANS
 ARE INDICATING 98' WHICH IS INCORRECT. UNTIL COMMENT #1
 IS ADDRESSED AND PLANS CORRELATED GAS WILL CONTINUE TO
 FAIL PLAN REVIEW. THE UNDERGROUND PE PIPING TO THE
 GENERATOR IS UNDERSIZED. THE FBC- FUEL GAS TABLE
 402.4(20) FOR 1-1/2" PE @ 125' IS ONLY GOOD FOR 550,000
 BTU'S, HOWEVER THE PLANS ARE INDICATING A BTU LOAD
 CAPACITY FOR THE GENERATOR AS BEING 1,012,000 BTU'S.
 THE FBC- FUEL GAS TABLE 402.4(20) @ 125' ONLY GOES UP
 TO 2" PIPE WHICH IS ONLY GOOD FOR 871,000 BTU'S. PLEASE
 REFERENCE THE ATTACHED GAS TABLES INDICATING THIS.
 PLEASE PROVIDE A SIZING TABLE INDICATING COMPLIANCE OR
 CHANGE SYSTEM TO A 2 PSI DELIVERY PRESSURE.
  
 3. SHEET P-1.1 AND P-2.1 PLEASE CORRELATE GENERATOR
 WITH ELECTRICAL SHEETS E-21 AND E-3.1 AND INDICATE THE
 GENERATOR A "FUTURE" APPLIANCE. NOTE: GENERATOR IS
 UNDER A SEPERATE PERMIT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  