| 2008-06-27 13:40:20 | ** DENIED REVISION ** |
| | |
| | ** ELECTRICAL RISER HAS NOW BEEN COMPLETELY REVISED |
| | ONCE AGAIN. |
| | ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER |
| | TRADES. |
| | |
| | ** GENERATOR IS NOT PART OF THE ELECTRICAL REVIEW. |
| | NIC. |
| | |
| | 1) NOTE: RISER SHOWS NEW ATS ON THE LINE SIDE OF THE |
| | MDP WHICH IS OK, HOWEVER THE SPECS SUBMITTED ARE NOT |
| | FOR A SERVICE ENTRANCE RATED TRANSFER SWITCH. |
| | 230.70,230.76,230.76, 110.3, 90.7 |
| | FBC 106.1.1, 106.1.2 FOR COORDINATION, CLARITY AND |
| | ADDITIONAL INFORMATION. |
| | |
| | 2) NOTE: PLEASE SEE RISER SHOWS MDP AS MLO (MAIN LUG |
| | ONLY) YET THEMDP ON PANEL SCHEDULE SHOWS THIS |
| | CONTAINING A MAIN. |
| | 230.70, 408.4, )225.31-225.39 |
| | FBC 106.1.1, 106.1.2 FOR CLARITY, ADDITIONAL |
| | INFORMATION AND COORDINATION OF PLANS. |
| | |
| | 3) NOTE: PLEASE SEE NEW STEAM GENERATOR WHICH IS SHOWN |
| | AS A 6KW LOAD ON A 1-POLE 20AMP CIRCUIT. |
| | PLEASE ADJUST. |
| | 310.16, 240.4 ETC |
| | |
| | 4) NOTE: PLEASE EXPLAIN NEW SHEET E-3.1 WHICH SHOWS |
| | SEVERAL NEW DETAILS FOR THIS PROJECT. PLEASE KNOW IF |
| | THESE DETAILS INCLUDING NEW GROUND BAR IS GOING TO BE |
| | USED THIS WOULD BE DIFFERENT FROM THE RISER GROUNDING |
| | ELECTRODE SYSTEM. |
| | THIS WOULD ALSO REQUIRE OTHER GROUNDING ELECTRODE |
| | METHODS. ARE ALL DETAILS ON THIS SHEET INTENDED? |
| | PLEASE COORDINATE. |
| | 250.50 |
| | FBC 106.1.1 FOR CLARITY. |
| | |
| | ONCE AGAINIF THERE ARE ANY QUESTIONS OR COMMENTS |
| | PLEASE CALL. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |