2008-06-27 13:40:20** DENIED REVISION **
  
 ** ELECTRICAL RISER HAS NOW BEEN COMPLETELY REVISED
 ONCE AGAIN.
 ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES.
  
 ** GENERATOR IS NOT PART OF THE ELECTRICAL REVIEW.
 NIC.
  
 1) NOTE: RISER SHOWS NEW ATS ON THE LINE SIDE OF THE
 MDP WHICH IS OK, HOWEVER THE SPECS SUBMITTED ARE NOT
 FOR A SERVICE ENTRANCE RATED TRANSFER SWITCH.
 230.70,230.76,230.76, 110.3, 90.7
 FBC 106.1.1, 106.1.2 FOR COORDINATION, CLARITY AND
 ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE RISER SHOWS MDP AS MLO (MAIN LUG
 ONLY) YET THEMDP ON PANEL SCHEDULE SHOWS THIS
 CONTAINING A MAIN.
 230.70, 408.4, )225.31-225.39
 FBC 106.1.1, 106.1.2 FOR CLARITY, ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
  
 3) NOTE: PLEASE SEE NEW STEAM GENERATOR WHICH IS SHOWN
 AS A 6KW LOAD ON A 1-POLE 20AMP CIRCUIT.
 PLEASE ADJUST.
 310.16, 240.4 ETC
  
 4) NOTE: PLEASE EXPLAIN NEW SHEET E-3.1 WHICH SHOWS
 SEVERAL NEW DETAILS FOR THIS PROJECT. PLEASE KNOW IF
 THESE DETAILS INCLUDING NEW GROUND BAR IS GOING TO BE
 USED THIS WOULD BE DIFFERENT FROM THE RISER GROUNDING
 ELECTRODE SYSTEM.
 THIS WOULD ALSO REQUIRE OTHER GROUNDING ELECTRODE
 METHODS. ARE ALL DETAILS ON THIS SHEET INTENDED?
 PLEASE COORDINATE.
 250.50
 FBC 106.1.1 FOR CLARITY.
  
 ONCE AGAINIF THERE ARE ANY QUESTIONS OR COMMENTS
 PLEASE CALL.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  