Plan Review Notes
Plan Review Notes For Permit 07040908
Permit Number 07040908
Review Stop Z
Sequence Number 2
Notes
Date Text
2008-06-24 14:18:22***FAILED - ZONING 2ND REVIEW***
  
  
 REPEAT COMMENTS:
  
 2)DEMOLITION/ADDITION PLANS SHALL BE STAMPED AND
 APPROVED BY THE CITY'S HISTORIC PRESERVATION
 DEPARTMENT.
  
 5)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.PLEASE SUBMIT A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZLDRS.
  
 6)ELECTRICAL SITE PLAN (SHEET ES -1) SHOWS A
 GENERATOR.INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.NOTE: THE GENERATOR MUST MAINTAIN A MINIMUM
 SETBACK OF 11 FEET TO THE REAR (WEST) PROPERTY LINE.
  
  
 NEW COMMENT:
  
 1)THE SIDE SETBACK IS NOT CLEARLY SHOWN FROM THE
 PROPERTY LINE TO THE NEW ADDITION.INDICATE THIS
 SETBACK DIMENSION ON THE SITE PLAN.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "E" - DP