| 2008-05-21 13:48:49 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) AS NOTED IN LAST REVIEW 4-1-08 NOTE #1. ENERGY |
| | CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER |
| | 2004 FBC 13-103.3. |
| | |
| | 2) AS NOTED IN LAST REVIEW 4-1-08 NOTE #6. PLEASE |
| | SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S THAT |
| | SHOW THE SUPPLY AIR VENTS COMPLY WITH 2004 FBC M1601.16 |
| | REGISTERS, GRILLES AND DIFFUSERS.DUCT REGISTERS, |
| | GRILLES AND DIFFUSERS SHALL HAVE A FLAME SPREAD RATING |
| | NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE |
| | COMBUSTION AND A SMOKE-DEVELOPED RATING NOT OVER 50 |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E 84. THE RESPONSE |
| | RECEIVED REFERS TO UL94 HB THAT DEALS WITH FLAME |
| | RATING, NOT FLAME SPREAD RATING AND SMOKE-DEVELOPED |
| | RATING. PLEASE PROVIDE DOCUMENTATION SHOWING THE FLAME |
| | SPREAD RATING AND SMOKE-DEVELOPED RATING. |
| | |
| | 3) NOT NOTED IN LAST REVIEW, THE GAS TANKLESS WATER |
| | HEATER IS IN A CONFINED SPACE WITH A CLOTHES DRYER. |
| | PLEASE PROVIDE FOR COMBUSTION AND MAKE-UP AIR PER 2004 |
| | FBC/R G2407.1, G2407.4, AND G2407.5.1. |
| | |
| | 4) NOT NOTED IN LAST REVIEW, THE PROPERTY IS IN FLOOD |
| | ZONE 'A5' PLEASE SHOW HOW THE A/C CONDENSER UNITS AND |
| | GENERATOR WILL BE MAINTAINED 6" ABOVE THE BASE FLOOD |
| | ELEVATION, PER W.P.B. CITY ORDINANCE CHAPTER 94, |
| | ARTICLE XVII SECTION 94-543. |
| | |