2008-05-21 13:48:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 4-1-08 NOTE #1. ENERGY
 CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER
 2004 FBC 13-103.3.
  
 2) AS NOTED IN LAST REVIEW 4-1-08 NOTE #6. PLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S THAT
 SHOW THE SUPPLY AIR VENTS COMPLY WITH 2004 FBC M1601.16
 REGISTERS, GRILLES AND DIFFUSERS.DUCT REGISTERS,
 GRILLES AND DIFFUSERS SHALL HAVE A FLAME SPREAD RATING
 NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE
 COMBUSTION AND A SMOKE-DEVELOPED RATING NOT OVER 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. THE RESPONSE
 RECEIVED REFERS TO UL94 HB THAT DEALS WITH FLAME
 RATING, NOT FLAME SPREAD RATING AND SMOKE-DEVELOPED
 RATING. PLEASE PROVIDE DOCUMENTATION SHOWING THE FLAME
 SPREAD RATING AND SMOKE-DEVELOPED RATING.
  
 3) NOT NOTED IN LAST REVIEW, THE GAS TANKLESS WATER
 HEATER IS IN A CONFINED SPACE WITH A CLOTHES DRYER.
 PLEASE PROVIDE FOR COMBUSTION AND MAKE-UP AIR PER 2004
 FBC/R G2407.1, G2407.4, AND G2407.5.1.
  
 4) NOT NOTED IN LAST REVIEW, THE PROPERTY IS IN FLOOD
 ZONE 'A5' PLEASE SHOW HOW THE A/C CONDENSER UNITS AND
 GENERATOR WILL BE MAINTAINED 6" ABOVE THE BASE FLOOD
 ELEVATION, PER W.P.B. CITY ORDINANCE CHAPTER 94,
 ARTICLE XVII SECTION 94-543.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]