Plan Review Notes
Plan Review Notes For Permit 07040908
Permit Number 07040908
Review Stop G
Sequence Number 2
Notes
Date Text
2008-05-30 10:02:31GAS PLAN REVIEW:
 DENIED REVISION:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
 NOTE: A GAS PERMIT WILL BE REQUIRED FOR THE PROPOSED
 WORK.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED NATURAL GAS RISER DIAGRAM ON SHEET
 P-2.1 IS NOT AN ISOMETRIC AND IT DOES NOT CLEARLY
 INDICATE ALL CUT SECTIONS OF PIPE WITH CORRESPONDING
 LENGTHS.
  
 2. SHEET P-1.1 FIRST FLOOR PLAN INDICATES THE GAS
 WATER HEATER IN A CONFINED SPACE WITH THE DRYER. SUBMIT
 CALCULATIONS FOR COMBUSTION
 AIR AND MAKEUP AIR PER FBC-2004 FUEL GAS CODE SECTION
 304.
  
 3. NOTE: A RESIDENTIAL GENERATOR PERMIT IS REQUIRED
 FOR THE GENERATOR. THE LOCATION OF THE GENERATOR NEEDS
 TO APPROVED BY ZONING BEFORE A GAS PERMIT CAN BE
 ISSUED. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY
 CLEARLY INDICATING THE GENERATOR'S LOCATION AND
 DIMENSIONS FROM PROPERTY LINES AND DISTANCES FROM
 ADJACENT STRUCTURES.
  
 4. SHEET P-2.1 GAS ISOMETRIC THE BTU'S FOR THE
 GENERATOR ARE WRONG. PER THE SUBMITED MANUFACTURER'S
 SPECIFICATIONS THE GENERATOR @ 100% STANBY RATING IS
 790,000. PLEASE CORRECT BOTH THE BTU'S INDICATED FOR
 THE GENERATOR AND THE TOTAL BTU'S FOR THE SYSTEM TO
 1,160,000.
  
 5. PER (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION
 AND STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 APPLICATION FOR A PERMIT.
 NOTE: ONLY ONE COPY OF THE GENERATOR MANUFACTURER'S
 SPECIFICATIONS WAS SUBMITTED.
  
 6. THE SUBMITTED GENERATOR MANUFACTURER'S
 SPECIFICATIONS FAIL TO INDICATE GENERATOR'S REQUIRED
 SETBACKS FROM STRUCTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  