| 2008-05-30 10:02:31 | GAS PLAN REVIEW: |
| | DENIED REVISION: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | NOTE: A GAS PERMIT WILL BE REQUIRED FOR THE PROPOSED |
| | WORK. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | NOTE: THE SUBMITTED NATURAL GAS RISER DIAGRAM ON SHEET |
| | P-2.1 IS NOT AN ISOMETRIC AND IT DOES NOT CLEARLY |
| | INDICATE ALL CUT SECTIONS OF PIPE WITH CORRESPONDING |
| | LENGTHS. |
| | |
| | 2. SHEET P-1.1 FIRST FLOOR PLAN INDICATES THE GAS |
| | WATER HEATER IN A CONFINED SPACE WITH THE DRYER. SUBMIT |
| | CALCULATIONS FOR COMBUSTION |
| | AIR AND MAKEUP AIR PER FBC-2004 FUEL GAS CODE SECTION |
| | 304. |
| | |
| | 3. NOTE: A RESIDENTIAL GENERATOR PERMIT IS REQUIRED |
| | FOR THE GENERATOR. THE LOCATION OF THE GENERATOR NEEDS |
| | TO APPROVED BY ZONING BEFORE A GAS PERMIT CAN BE |
| | ISSUED. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY |
| | CLEARLY INDICATING THE GENERATOR'S LOCATION AND |
| | DIMENSIONS FROM PROPERTY LINES AND DISTANCES FROM |
| | ADJACENT STRUCTURES. |
| | |
| | 4. SHEET P-2.1 GAS ISOMETRIC THE BTU'S FOR THE |
| | GENERATOR ARE WRONG. PER THE SUBMITED MANUFACTURER'S |
| | SPECIFICATIONS THE GENERATOR @ 100% STANBY RATING IS |
| | 790,000. PLEASE CORRECT BOTH THE BTU'S INDICATED FOR |
| | THE GENERATOR AND THE TOTAL BTU'S FOR THE SYSTEM TO |
| | 1,160,000. |
| | |
| | 5. PER (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION |
| | AND STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA |
| | SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH |
| | APPLICATION FOR A PERMIT. |
| | NOTE: ONLY ONE COPY OF THE GENERATOR MANUFACTURER'S |
| | SPECIFICATIONS WAS SUBMITTED. |
| | |
| | 6. THE SUBMITTED GENERATOR MANUFACTURER'S |
| | SPECIFICATIONS FAIL TO INDICATE GENERATOR'S REQUIRED |
| | SETBACKS FROM STRUCTURES. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |