2008-06-03 10:54:06** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: AS THE ORIGINAL PERMIT APPLIED AS 06040626 DID
 NOT CONTAIN SUB PERMITS, INSPECTIONS FOR MEP AND DID
 NOT OBTAIN FINAL INSPECTIONS, PLANS MUST GO BACK TO
 ZONING FOR REVIEW AND STAMPING. THERE ARE SOME ITEMS ON
 PLANS CHANGED WHICH WERE NOT ON ORIGINAL PLANS STAMPED
 BY ZONING.
 ALL REVISED PLANS MUST ALSO CONTAIN HISTORIC REVIEW AND
 STAMPS. PLANS WILL BE ROUTED TO ZONING.
  
 2) NOTE: AS STATED ON PREVIOUS REVIEW THE GENERATOR WAS
 NOT INCLUDED ON ORIGINAL PLANS AND NEEDS TO BE DONE
 UNDER A SEPARATE PERMIT. THE ATS MAY BE INCLUDED WITH
 ELECTRICAL SERVICE HOWEVER PLEASE SEE THE ATS MUST MEET
 THE FOLLOWING.
 PLEASE SEE THE SIZE IS STILL SHOWN AS 260AMPS WHICH IS
 NOT A STANDARD RECOGNIZED IN THE NEC 240.6.
 110.3, 90.7.
  
 3) NOTE: PLEASE KNOW DISCONNECTING MEANS PER
 225.31-225.39 SHALL BE INSTALLED. BASED ON PLANS THERE
 IS NO DISCONNECTING MEANS FOR FEEDERS FROM GENERATOR AT
 MAIN HOUSE.
 PLEASE KNOW AS SHOWN THIS DOES NOT APPEAR TO MEET THE
 EXCEPTION IN 702.11.
 THIS ONLY NEEDS TO BE A DISCONNECT RATED FOR LOAD
 SERVED AND NOT A DISCONNECT WITH OVER CURRENT
 PROTECTION.
  
 4) NOTE: PLEASE SEE ALL RECEPTACLES SERVING KITCHEN
 COUNTER SPACE ARE REQUIRED TO BE GFI/GFI PROTECTED PER
 210.8A6. THIS WOULD INCLUDE KITCHEN ISLAND. THIS CAN BE
 REDLINED IF ONLY COMMENT REMAINING OR IF PAGE DOES NOT
 NEED TO BE REVISED FOR ANY OTHER COMMENTS.
  
 5) NOTE: PLEASE SEE ELECTRICAL RISER IS SHOWING AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT AND BEFORE FPL METER WHICH IS NOT
 PERMITTED.
 PLEASE SEE 250.6, 250.24
 ** EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AS
 1500VA SHALL BE FIGURE FOR EACH OF THE SMALL APPLIANCE
 CIRCUITS.
 THERE ARE A GREATER NUMBER OF SMALL APPLIANCE CIRCUITS
 ON PANEL SCHEDULES THAN SHOWN ON LOAD CALCULATIONS.
  
 7) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE SHALL
 BE DETAILED FOR CIRCUITS IN WHICH THEY FEED. THIS WILL
 AFFECT THE NOTE #6 ABOVE AS CIRCUIT #1 IS ACTUALLY A
 REFRIGERATOR.
 PLEASE SEE THE FOLLOWING TEXT EXTRACTED FROM THE NEC.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 8) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS ON EACH
 PANEL. PANELS ARE SHOWN AS 400AMP AND NOW SERVICE WHICH
 WAS PREVIOUSLY 400AMPS IS NOW 250AMPS. HOWEVER FEEDERS
 ARE STILL SHOWN FOR 400AMPS?
 EACH PANEL NOTES TO SEE LOAD CALCULATIONS FOR LOADS ON
 PANELS HOWEVER BASED ON THE LOADS SHOWN ON SHEET ONLY
 THE LOAD FOR ENTIRE SERVICE IS SHOWN.
 PLEASE SUBMIT AND COORDINATE.
 220, 215.5, 310.16, 240.4 ETC
 FBC 106.1.2 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 9) NOTE: PLEASE SEE THE PANEL *A* SHOWS A AHU/CU #3,
 HOWEVER SO DOES PANEL *B*.
 PLANS SHOW FOUR SYSTEMS.
 PLEASE SEE PLANS ON E-1.1 AS BOTH THE CU#1 AND CU#4 ARE
 SHOWN ON SAME CIRCUITS A-33/35. THIS IS NOT POSSIBLE.
 PLEASE COORDINATE. 408.4
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE ELEVATOR SHOWS A 10KW LOAD ON A
 30AMP CIRCUIT. THIS CAN NOT BE POSSIBLE AS 10KW EXCEEDS
 THE RATING OF THE 30AMP CIRCUIT.
 310.16, 240.4 ETC
 PLEASE VERIFY LOAD ON ELEVATOR.
  
 11) NOTE: PLEASE SEE 110.26 AS NOT ALL THE CU
 DISCONNECT MEET MINIMUM CLEARANCES.
  
 12) NOTE: PLEASE KNOW *GATES* ARE NOT INCLUDED IN SCOPE
 OF WORK.
  
 13) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE#9 PLEASE
 COORDINATE ALL CIRCUITING ON PLANS WITH THAT OF THE
 CIRCUITS ON PANEL SCHEDULES.
 FBC 106.3.5.4, 106.1.2, NEC 408.4.
 THE FEW NOTED ABOVE IS NOT AN EXHAUSTED LIST AND ONLY
 REFERENCE A FEW FOR EXAMPLES.
  
 14) NOTE: PLEASE KNOW AS NOTED IN PREVIOUS REVIEW THE
 LOCATIONS OF THE FIXTURES IN CLOSETS DO NOT APPEAR TO
 MEET 410.8 WITH THE MINIMUM SHELVING DISTANCES GIVEN BY
 THE CODE. THE PLANS NOTE ON WALL ABOVE DOOR OR ON
 CEILINGS.THERE MAY BE THE MINIMUM NEEDED PER CODE FOR
 LOCATIONS ABOVE DOOR HOWEVER THE LOCATIONS ON CEILINGS
 FOR SOME OF THESE DO NOT APPEAR THIS WILL MEET CODE.
 THE PLANS ALSO CALL FOR THE FIXTURE TO BE CHOSEN BY
 OWNER/ARCHITECT HOWEVER THE MINIMUM SHALL BE SHOWN ON
 PLANS AT THIS TIME FOR THE TYPE OF FIXTURES TO COMPLY
 WITH MINIMUM SAFETY AND FIRE CONCERNS.
 THIS IS A FIRE/ LIFE SAFETY HAZARD AND ONE REASON MANY
 FIRES ARE STARTED IN CLOSETS AND STORAGE AREAS WHICH
 EASILY IGNITABLE MATERIALS ARE LOCATED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717