| 2008-06-03 10:54:06 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: AS THE ORIGINAL PERMIT APPLIED AS 06040626 DID |
| | NOT CONTAIN SUB PERMITS, INSPECTIONS FOR MEP AND DID |
| | NOT OBTAIN FINAL INSPECTIONS, PLANS MUST GO BACK TO |
| | ZONING FOR REVIEW AND STAMPING. THERE ARE SOME ITEMS ON |
| | PLANS CHANGED WHICH WERE NOT ON ORIGINAL PLANS STAMPED |
| | BY ZONING. |
| | ALL REVISED PLANS MUST ALSO CONTAIN HISTORIC REVIEW AND |
| | STAMPS. PLANS WILL BE ROUTED TO ZONING. |
| | |
| | 2) NOTE: AS STATED ON PREVIOUS REVIEW THE GENERATOR WAS |
| | NOT INCLUDED ON ORIGINAL PLANS AND NEEDS TO BE DONE |
| | UNDER A SEPARATE PERMIT. THE ATS MAY BE INCLUDED WITH |
| | ELECTRICAL SERVICE HOWEVER PLEASE SEE THE ATS MUST MEET |
| | THE FOLLOWING. |
| | PLEASE SEE THE SIZE IS STILL SHOWN AS 260AMPS WHICH IS |
| | NOT A STANDARD RECOGNIZED IN THE NEC 240.6. |
| | 110.3, 90.7. |
| | |
| | 3) NOTE: PLEASE KNOW DISCONNECTING MEANS PER |
| | 225.31-225.39 SHALL BE INSTALLED. BASED ON PLANS THERE |
| | IS NO DISCONNECTING MEANS FOR FEEDERS FROM GENERATOR AT |
| | MAIN HOUSE. |
| | PLEASE KNOW AS SHOWN THIS DOES NOT APPEAR TO MEET THE |
| | EXCEPTION IN 702.11. |
| | THIS ONLY NEEDS TO BE A DISCONNECT RATED FOR LOAD |
| | SERVED AND NOT A DISCONNECT WITH OVER CURRENT |
| | PROTECTION. |
| | |
| | 4) NOTE: PLEASE SEE ALL RECEPTACLES SERVING KITCHEN |
| | COUNTER SPACE ARE REQUIRED TO BE GFI/GFI PROTECTED PER |
| | 210.8A6. THIS WOULD INCLUDE KITCHEN ISLAND. THIS CAN BE |
| | REDLINED IF ONLY COMMENT REMAINING OR IF PAGE DOES NOT |
| | NEED TO BE REVISED FOR ANY OTHER COMMENTS. |
| | |
| | 5) NOTE: PLEASE SEE ELECTRICAL RISER IS SHOWING AN |
| | *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS |
| | OF DISCONNECT AND BEFORE FPL METER WHICH IS NOT |
| | PERMITTED. |
| | PLEASE SEE 250.6, 250.24 |
| | ** EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AS |
| | 1500VA SHALL BE FIGURE FOR EACH OF THE SMALL APPLIANCE |
| | CIRCUITS. |
| | THERE ARE A GREATER NUMBER OF SMALL APPLIANCE CIRCUITS |
| | ON PANEL SCHEDULES THAN SHOWN ON LOAD CALCULATIONS. |
| | |
| | 7) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE SHALL |
| | BE DETAILED FOR CIRCUITS IN WHICH THEY FEED. THIS WILL |
| | AFFECT THE NOTE #6 ABOVE AS CIRCUIT #1 IS ACTUALLY A |
| | REFRIGERATOR. |
| | PLEASE SEE THE FOLLOWING TEXT EXTRACTED FROM THE NEC. |
| | SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | 8) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS ON EACH |
| | PANEL. PANELS ARE SHOWN AS 400AMP AND NOW SERVICE WHICH |
| | WAS PREVIOUSLY 400AMPS IS NOW 250AMPS. HOWEVER FEEDERS |
| | ARE STILL SHOWN FOR 400AMPS? |
| | EACH PANEL NOTES TO SEE LOAD CALCULATIONS FOR LOADS ON |
| | PANELS HOWEVER BASED ON THE LOADS SHOWN ON SHEET ONLY |
| | THE LOAD FOR ENTIRE SERVICE IS SHOWN. |
| | PLEASE SUBMIT AND COORDINATE. |
| | 220, 215.5, 310.16, 240.4 ETC |
| | FBC 106.1.2 FOR COORDINATION AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 9) NOTE: PLEASE SEE THE PANEL *A* SHOWS A AHU/CU #3, |
| | HOWEVER SO DOES PANEL *B*. |
| | PLANS SHOW FOUR SYSTEMS. |
| | PLEASE SEE PLANS ON E-1.1 AS BOTH THE CU#1 AND CU#4 ARE |
| | SHOWN ON SAME CIRCUITS A-33/35. THIS IS NOT POSSIBLE. |
| | PLEASE COORDINATE. 408.4 |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE ELEVATOR SHOWS A 10KW LOAD ON A |
| | 30AMP CIRCUIT. THIS CAN NOT BE POSSIBLE AS 10KW EXCEEDS |
| | THE RATING OF THE 30AMP CIRCUIT. |
| | 310.16, 240.4 ETC |
| | PLEASE VERIFY LOAD ON ELEVATOR. |
| | |
| | 11) NOTE: PLEASE SEE 110.26 AS NOT ALL THE CU |
| | DISCONNECT MEET MINIMUM CLEARANCES. |
| | |
| | 12) NOTE: PLEASE KNOW *GATES* ARE NOT INCLUDED IN SCOPE |
| | OF WORK. |
| | |
| | 13) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE#9 PLEASE |
| | COORDINATE ALL CIRCUITING ON PLANS WITH THAT OF THE |
| | CIRCUITS ON PANEL SCHEDULES. |
| | FBC 106.3.5.4, 106.1.2, NEC 408.4. |
| | THE FEW NOTED ABOVE IS NOT AN EXHAUSTED LIST AND ONLY |
| | REFERENCE A FEW FOR EXAMPLES. |
| | |
| | 14) NOTE: PLEASE KNOW AS NOTED IN PREVIOUS REVIEW THE |
| | LOCATIONS OF THE FIXTURES IN CLOSETS DO NOT APPEAR TO |
| | MEET 410.8 WITH THE MINIMUM SHELVING DISTANCES GIVEN BY |
| | THE CODE. THE PLANS NOTE ON WALL ABOVE DOOR OR ON |
| | CEILINGS.THERE MAY BE THE MINIMUM NEEDED PER CODE FOR |
| | LOCATIONS ABOVE DOOR HOWEVER THE LOCATIONS ON CEILINGS |
| | FOR SOME OF THESE DO NOT APPEAR THIS WILL MEET CODE. |
| | THE PLANS ALSO CALL FOR THE FIXTURE TO BE CHOSEN BY |
| | OWNER/ARCHITECT HOWEVER THE MINIMUM SHALL BE SHOWN ON |
| | PLANS AT THIS TIME FOR THE TYPE OF FIXTURES TO COMPLY |
| | WITH MINIMUM SAFETY AND FIRE CONCERNS. |
| | THIS IS A FIRE/ LIFE SAFETY HAZARD AND ONE REASON MANY |
| | FIRES ARE STARTED IN CLOSETS AND STORAGE AREAS WHICH |
| | EASILY IGNITABLE MATERIALS ARE LOCATED. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |