| Date |
Text |
| 2008-06-09 15:14:52 | ***FAILED - ZONING 1ST REVIEW*** |
| | |
| | |
| | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH |
| | INCLUDES THE PROPERTY'S LEGAL DESCRIPTION AND ADDRESS. |
| | |
| | 2)DEMOLITION/ADDITION PLANS SHALL BE STAMPED AND |
| | APPROVED BY THE CITY'S HISTORIC PRESERVATION |
| | DEPARTMENT. |
| | |
| | 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C |
| | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION |
| | 94-305(B)(4) OF THE CITY'S ZONING AND LAND DEVELOPMENT |
| | REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT MAY NOT |
| | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. |
| | |
| | 4)INDICATE OVERHANG DIMENSIONS OF THE PROPOSED |
| | ADDITION.AS PER SECTION 94-305(B) OF THE ZLDRS: |
| | OVERHANGS MAY NOT PROJECT MORE THAN 3' INTO A REQUIRED |
| | SETACK. |
| | |
| | 5)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND |
| | LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF |
| | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE |
| | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY |
| | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE |
| | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF |
| | THE ZLDRS.PLEASE SUBMIT A LANDSCAPE PLAN SHOWING |
| | COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE |
| | ZLDRS. |
| | |
| | 6)ELECTRICAL SITE PLAN (SHEET ES -1) SHOWS A |
| | GENERATOR.INDICATE SETBACK DIMENSIONS FROM PROPOSED |
| | GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER |
| | SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND |
| | DEVELOPMENT REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT |
| | MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED |
| | SETBACK.NOTE: THE GENERATOR MUST MAINTAIN A MINIMUM |
| | SETBACK OF 11 FEET TO THE REAR (WEST) PROPERTY LINE. |
| | |
| | |
| | NOTE:THE "FUTURE LIBRARY CONSTRUCTION - TO BE |
| | PERMITTED SEPARATELY" WILL NOT BE ALLOWED AS SHOWN. IF |
| | THE PRINCIPAL STRUCTURE IS MADE TO CONNECT TO THE |
| | EXISTING ACCESSORY STRUCTURE, THE ENTIRE BUILDING WILL |
| | BE REQUIRED TO MEET THE PRINCIPAL STRUCTURE'S SETBACK |
| | REQUIREMENTS, WHICH IT DOES NOT. |
| | |
| | |
| | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, |
| | ZONING TECHNICIAN (561)805-6720 |