Plan Review Notes
Plan Review Notes For Permit 07040908
Permit Number 07040908
Review Stop M
Sequence Number 1
Notes
Date Text
2008-04-01 14:25:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) COOLING LOAD CALCULATIONS FOR SYSTEM #1 ARE CALLING
 FOR 23,300 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE
 SHOWING A SYSTEM WITH 33,000 TOTAL COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 3 TON SYSTEM IS
 TO LARGE PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS FOR SYSTEM #2 ARE CALLING
 FOR 31,200 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE
 SHOWING A SYSTEM WITH 44,000 TOTAL COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 4 TON SYSTEM IS
 TO LARGE PLEASE CORRECT.
  
 4) COOLING LOAD CALCULATIONS FOR SYSTEM #3 ARE CALLING
 FOR 34,300 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE
 SHOWING A SYSTEM WITH 54,000 TOTAL COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 5 TON SYSTEM IS
 TO LARGE PLEASE CORRECT.
  
 5) PLEASE SUBMIT MANUAL D CALCULATIONS OR EQUIVALENT
 FOR RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND
 FBC 13-610.1.ABC.1.
  
 6) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 SUPPLY AIR VENTS TO SHOW THEY COMPLY WITH 2004 FBC
 M1601.16 REGISTERS, GRILLES AND DIFFUSERS.DUCT
 REGISTERS, GRILLES AND DIFFUSERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS, AND SHALL HAVE A FLAME SPREAD RATING NOT
 OVER 25 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE
 COMBUSTION AND A SMOKE-DEVELOPED RATING NOT OVER 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. BALANCING
 DAMPERS OR OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL
 BE PROVIDED IN THE BRANCH DUCTS OR AT EACH INDIVIDUAL
 DUCT REGISTER, GRILLE OR DIFFUSER.
  
 7) THE VALUE ON THE PERMIT MUST BE ADJUSTED TO THE FAIR
 MARKET VALUE (REPLACEMENT VALUE) FOR THE RENOVATION
 WITH ALL MATERIALS AND LABOR. IF THE VALUE IS NOT
 ADJUSTED THEN THE CITY WILL NEED TO ADJUST IT USING THE
 MARSHALL & SWIFT NATIONAL VALUATION SERVICE, PER 2004
 WPB AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]