| 2008-04-01 14:25:38 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-103.3. |
| | |
| | 2) COOLING LOAD CALCULATIONS FOR SYSTEM #1 ARE CALLING |
| | FOR 23,300 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE |
| | SHOWING A SYSTEM WITH 33,000 TOTAL COOLING BTU'S. THE |
| | PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD |
| | CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 3 TON SYSTEM IS |
| | TO LARGE PLEASE CORRECT. |
| | |
| | 3) COOLING LOAD CALCULATIONS FOR SYSTEM #2 ARE CALLING |
| | FOR 31,200 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE |
| | SHOWING A SYSTEM WITH 44,000 TOTAL COOLING BTU'S. THE |
| | PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD |
| | CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 4 TON SYSTEM IS |
| | TO LARGE PLEASE CORRECT. |
| | |
| | 4) COOLING LOAD CALCULATIONS FOR SYSTEM #3 ARE CALLING |
| | FOR 34,300 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE |
| | SHOWING A SYSTEM WITH 54,000 TOTAL COOLING BTU'S. THE |
| | PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD |
| | CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 5 TON SYSTEM IS |
| | TO LARGE PLEASE CORRECT. |
| | |
| | 5) PLEASE SUBMIT MANUAL D CALCULATIONS OR EQUIVALENT |
| | FOR RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND |
| | FBC 13-610.1.ABC.1. |
| | |
| | 6) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| | SUPPLY AIR VENTS TO SHOW THEY COMPLY WITH 2004 FBC |
| | M1601.16 REGISTERS, GRILLES AND DIFFUSERS.DUCT |
| | REGISTERS, GRILLES AND DIFFUSERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS, AND SHALL HAVE A FLAME SPREAD RATING NOT |
| | OVER 25 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE |
| | COMBUSTION AND A SMOKE-DEVELOPED RATING NOT OVER 50 |
| | WHEN TESTED IN ACCORDANCE WITH ASTM E 84. BALANCING |
| | DAMPERS OR OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL |
| | BE PROVIDED IN THE BRANCH DUCTS OR AT EACH INDIVIDUAL |
| | DUCT REGISTER, GRILLE OR DIFFUSER. |
| | |
| | 7) THE VALUE ON THE PERMIT MUST BE ADJUSTED TO THE FAIR |
| | MARKET VALUE (REPLACEMENT VALUE) FOR THE RENOVATION |
| | WITH ALL MATERIALS AND LABOR. IF THE VALUE IS NOT |
| | ADJUSTED THEN THE CITY WILL NEED TO ADJUST IT USING THE |
| | MARSHALL & SWIFT NATIONAL VALUATION SERVICE, PER 2004 |
| | WPB AMEND. 108.3. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |