2008-04-02 09:47:15DENIED;
 1. TYPE OF GAS, (LP OR NATURAL)
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. A GEN-RES. AND A ELECTRICAL PERMIT APPLICATION IS
 REQUIRED FOR GENERATOR. PROVIDE MANUFACTURE SPEC.
 SHEETS, ELECTICAL PLAN AND SURVEY.