| Notes |
| Date |
Text |
| 2008-04-02 09:47:15 | DENIED; | | | 1. TYPE OF GAS, (LP OR NATURAL) | | | 2. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | 3. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 4. A GEN-RES. AND A ELECTRICAL PERMIT APPLICATION IS | | | REQUIRED FOR GENERATOR. PROVIDE MANUFACTURE SPEC. | | | SHEETS, ELECTICAL PLAN AND SURVEY. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|