Plan Review Notes
Plan Review Notes For Permit 07040908
Permit Number 07040908
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-04 17:32:25** DENIED **
  
 1) NOTE: PLEASE SEE THAT COMPLETE PLANS INCLUDING PLANS
 FOR SITE AND SURVEY WILL BE REQUIRED TO BE SUBMITTED.
 NO GENERATOR WAS ON ORIGINAL PLANS WHICH ARE NOW
 CLOSED.
 PLEASE SEE THAT THE SUBMITTED PLANS FOR *STRUCTURAL
 ONLY SCOPE OF WORK* NEEDS TO INCLUDE ALL WORK WHICH DID
 NOT RECEIVE FINALS UNDER ORIGINAL APPLIED PERMIT
 06040626. THIS WILL INCLUDE THE ADDITION TO THE
 EXISTING DWELLING UNDER FIRE DAMAGE REPAIR ETC.
 THE NEW GENERATOR/ATS WAS NEVER PERMITTED OR APPLIED
 FOR.
  
 ** THERE WAS NEVER ANY ROUGH ELECTRICAL INSPECTION ON
 THE PREVIOUS ELECTRICAL PERMIT WHICH HAS EXPIRED.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK WHICH IS NOW BEING INCLUDED TO PREVIOUS APPLIED
 SCOPE OF WORK NOT COMPLETED NEEDS TO BE ADJUSTED.
 THE VALUE FOR ALL LABOR, MATERIALS EQUIPMENT ETC NEEDS
 TO BE INCLUDED. IF THE GENERATOR IS GOING TO BE UNDER
 THE SCOPE OF WORK THEN PLEASE KNOW VALUE SHALL INCLUDE
 THIS AS APPLIED VALUE.
 FBC 108.3
  
 3) NOTE: PLEASE SEE THAT SOME ITEMS WHICH ARE SHOWN AS
 EXISTING ON PLANS NEEDS TO BE SHOWN AS NEW AS THESE
 RECORD SET OF PLANS IS TO COMPLETE SCOPE OF WORK NEVER
 COMPLETED. THE NEW CONTRACTOR AND RECORD PLANS NEEDS TO
 SHOWS THESE.
 FOR EXAMPLE:
 OFFICE, ADDITION, ETC
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL LIGHT FIXTURES
 MISSING FOR ROOMS AND OUTDOOR LOCATIONS WHICH NEED
 FIXTURES PER 210.70, LS 101 7.8.
 MOST ARE SHOWN AS J-BOXES.
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE A
 250AMP SERVICE YET RISER SHOWS 400AMPS.
 FBC 106.1.2 FOR COORDINATION.
  
 6) NOTE: PLEASE VERIFY HOW SOME OF THE AHU/CU ON PANEL
 SCHEDULES HAVE NO LOADS SHOWN.
 FOR EXAMPLE:
 UNITS #2 AND 3.
 220
  
 7) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS ON
 GENERATOR AND ATS.
 PLEASE SEE 110.3, 90.7
 SLAB DETAILS NEEDED BY BUILDING.
 PLEASE ALSO KNOW THE HOUSE/LOCATION IS IN A FLOOD ZONE,
 ALL ELECTRICAL EQUIPMENT INCLUDING GENERATOR MUST BE
 6INCHES ABOVE BASE FLOOD ELEVATION.
  
 8) NOTE: PLEASE COMPLETE CIRCUITING FOR SMOKE ALARMS.
 PLEASE ALSO SEE NFPA-72 11.8.3 AS THE SMOKE ALARM IN
 MASTER BEDROOM IS NOT CODE COMPLIANT. NEEDS TO BE
 WITHIN 3FT OFPEAK AND WITHIN 12INCHES OF THE HIGHEST
 POINT.
  
 9) NOTE: PLEASE SEE FBC 13-606.1.ABC.1.2.4 FOR MINIMUM
 TYPES OF RECESSED LIGHTS.
  
 10) NOTE: PLEASE SEE LIGHTS IN SOME CLOSETS DO NOT MEET
 410.8 FOR MINIMUM CLEARANCES.
  
 11) NOTE: PLEASE SEE THE FEEDER SIZE SHOWN FROM THE
 GENERATOR IS SHOWN AS 150MCM. THIS IS NOT A CONDUCTOR
 SIZE PER AWG.
 110.3
  
 12) NOTE: CODES NEED TO BE STATED ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2004 FBC W/ 2007 (RESIDENTIAL CODE)
  
 13) NOTE: PLEASE SEE THE ELECTRICAL AND CONDUITS RUN
 OUTSIDE THE PROPERTY IN THE CITY RIGHT OF WAY ARE NOT
 PERMITTED.
 ALL ELECTRICAL MUST REMAIN WITHIN LOT LINES.
  
 14) NOTE: PLEASE COMPLETE FIXTURE LEGEND, AND SYMBOL
 LEGEND FOR THIS DWELLING. PLEASE SEE SHEET E-0.1 WHICH
 INDICATES MANY ITEMS FROM WHAT WOULD BE A COMMERCIAL
 BUILDING INCLUDING FIXTURES AND CONTROLS.
 FBC 106.3.5.4, 106.1.2
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW A FULL REVIEW COULD NOT BE DONE AT
 THIS TIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]