| 2008-04-04 17:32:25 | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THAT COMPLETE PLANS INCLUDING PLANS |
| | FOR SITE AND SURVEY WILL BE REQUIRED TO BE SUBMITTED. |
| | NO GENERATOR WAS ON ORIGINAL PLANS WHICH ARE NOW |
| | CLOSED. |
| | PLEASE SEE THAT THE SUBMITTED PLANS FOR *STRUCTURAL |
| | ONLY SCOPE OF WORK* NEEDS TO INCLUDE ALL WORK WHICH DID |
| | NOT RECEIVE FINALS UNDER ORIGINAL APPLIED PERMIT |
| | 06040626. THIS WILL INCLUDE THE ADDITION TO THE |
| | EXISTING DWELLING UNDER FIRE DAMAGE REPAIR ETC. |
| | THE NEW GENERATOR/ATS WAS NEVER PERMITTED OR APPLIED |
| | FOR. |
| | |
| | ** THERE WAS NEVER ANY ROUGH ELECTRICAL INSPECTION ON |
| | THE PREVIOUS ELECTRICAL PERMIT WHICH HAS EXPIRED. |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK WHICH IS NOW BEING INCLUDED TO PREVIOUS APPLIED |
| | SCOPE OF WORK NOT COMPLETED NEEDS TO BE ADJUSTED. |
| | THE VALUE FOR ALL LABOR, MATERIALS EQUIPMENT ETC NEEDS |
| | TO BE INCLUDED. IF THE GENERATOR IS GOING TO BE UNDER |
| | THE SCOPE OF WORK THEN PLEASE KNOW VALUE SHALL INCLUDE |
| | THIS AS APPLIED VALUE. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE SEE THAT SOME ITEMS WHICH ARE SHOWN AS |
| | EXISTING ON PLANS NEEDS TO BE SHOWN AS NEW AS THESE |
| | RECORD SET OF PLANS IS TO COMPLETE SCOPE OF WORK NEVER |
| | COMPLETED. THE NEW CONTRACTOR AND RECORD PLANS NEEDS TO |
| | SHOWS THESE. |
| | FOR EXAMPLE: |
| | OFFICE, ADDITION, ETC |
| | FBC 106.3.5.4 |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE SEVERAL LIGHT FIXTURES |
| | MISSING FOR ROOMS AND OUTDOOR LOCATIONS WHICH NEED |
| | FIXTURES PER 210.70, LS 101 7.8. |
| | MOST ARE SHOWN AS J-BOXES. |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE A |
| | 250AMP SERVICE YET RISER SHOWS 400AMPS. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 6) NOTE: PLEASE VERIFY HOW SOME OF THE AHU/CU ON PANEL |
| | SCHEDULES HAVE NO LOADS SHOWN. |
| | FOR EXAMPLE: |
| | UNITS #2 AND 3. |
| | 220 |
| | |
| | 7) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS ON |
| | GENERATOR AND ATS. |
| | PLEASE SEE 110.3, 90.7 |
| | SLAB DETAILS NEEDED BY BUILDING. |
| | PLEASE ALSO KNOW THE HOUSE/LOCATION IS IN A FLOOD ZONE, |
| | ALL ELECTRICAL EQUIPMENT INCLUDING GENERATOR MUST BE |
| | 6INCHES ABOVE BASE FLOOD ELEVATION. |
| | |
| | 8) NOTE: PLEASE COMPLETE CIRCUITING FOR SMOKE ALARMS. |
| | PLEASE ALSO SEE NFPA-72 11.8.3 AS THE SMOKE ALARM IN |
| | MASTER BEDROOM IS NOT CODE COMPLIANT. NEEDS TO BE |
| | WITHIN 3FT OFPEAK AND WITHIN 12INCHES OF THE HIGHEST |
| | POINT. |
| | |
| | 9) NOTE: PLEASE SEE FBC 13-606.1.ABC.1.2.4 FOR MINIMUM |
| | TYPES OF RECESSED LIGHTS. |
| | |
| | 10) NOTE: PLEASE SEE LIGHTS IN SOME CLOSETS DO NOT MEET |
| | 410.8 FOR MINIMUM CLEARANCES. |
| | |
| | 11) NOTE: PLEASE SEE THE FEEDER SIZE SHOWN FROM THE |
| | GENERATOR IS SHOWN AS 150MCM. THIS IS NOT A CONDUCTOR |
| | SIZE PER AWG. |
| | 110.3 |
| | |
| | 12) NOTE: CODES NEED TO BE STATED ON PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | 2004 FBC W/ 2007 (RESIDENTIAL CODE) |
| | |
| | 13) NOTE: PLEASE SEE THE ELECTRICAL AND CONDUITS RUN |
| | OUTSIDE THE PROPERTY IN THE CITY RIGHT OF WAY ARE NOT |
| | PERMITTED. |
| | ALL ELECTRICAL MUST REMAIN WITHIN LOT LINES. |
| | |
| | 14) NOTE: PLEASE COMPLETE FIXTURE LEGEND, AND SYMBOL |
| | LEGEND FOR THIS DWELLING. PLEASE SEE SHEET E-0.1 WHICH |
| | INDICATES MANY ITEMS FROM WHAT WOULD BE A COMMERCIAL |
| | BUILDING INCLUDING FIXTURES AND CONTROLS. |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET |
| | SUBMITTED FOR REVIEW A FULL REVIEW COULD NOT BE DONE AT |
| | THIS TIME. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |