| Plan Review Notes For Permit 07040881 |
| Permit Number |
07040881 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-01 13:49:47 | RE-STAMP*** DENIED*** | | | 1) THE RE-STAMP IS A REVISION. ENGINEERING FOR THE | | | PER-ENGINEERED A/C CONDENSER STANDS NEEDS TO BE A | | | PRODUCT APPROVAL OR NOA. SEE FS 553.842(1) AND FAC | | | 9B-72.010(31)(G). | | | | | | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|