| Plan Review Notes For Permit 07040875 |
| Permit Number |
07040875 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-31 12:24:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | | | | 1.)ENGINEER HAS SPECIFIED DESIGN PRESSURE OF -52.7, | | | BUT THE DOOR HAS A DESIGN PRESSURE LIMITATION OF -44.4 | | | FOR THE DOOR CIRCLED BY THE ENGINEER.NOTE THAT THE | | | HIGHER PRESSURE OF -65.6 IS THE TEST PRESSURE; DESIGN | | | PRESSURE HAS A FACTOR OF SAFETY. | | | | | | 2.)THIS BUILDING IS IN EXPOSURE C.REVISE WIND | | | DESIGN CRITERIA. | | | | | | OTHER ITEMS OK PER NMK | | | |
|