| 2007-07-10 11:43:32 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL |
| | AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT |
| | ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | 3RD REVIEW - NOT ADDRESSED.TENANT SEPARATION IS |
| | REQUIRED FBC708.1(5).THIS IS A SEPARATION BETWEEN A |
| | PRIVATE, OR "TENANT" SPACE, AND THE COMMON AREA. |
| | |
| | 2.)THE INFORMATION IN REGARDS TO THE EXISTING |
| | BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT |
| | LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE |
| | COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE |
| | INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE |
| | DESIGN PROFESSIONAL. |
| | |
| | 2ND & 3RD REVIEW - PROVIDE THE CODE SUMMARY AS |
| | REQUESTED; OCCUPANCY CLASSIFICATION FBC3, BUILDING TYPE |
| | FBC6, SPRINKLER INFORMATION.THIS WAS ADDRESSED IN THE |
| | RESPONSE LETTER BUT THE RESPONSE LETTER IS NOT A PART |
| | OF THE PERMIT PACKAGE.PLEASE INCORPORATE INTO THE |
| | PLAN. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.)ADDRESSED. |
| | |
| | 5.)PLANS STATE "RELOCATE FIRE SPRINKLER HEAD". |
| | PROVIDE A PLAN.THE FIRE SPRINKLER PLAN IS REQUIRED AS |
| | A PART OF THIS PERMIT PACKAGE FS553.79(2), |
| | FBC*106.3.5.1.1(5). |
| | |
| | 6.-7.)ADDRESSED. |
| | |
| | 8.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER |
| | OF RECORD, FBC*106.3.3. |
| | |
| | 9.)PROVIDE FIRE RATING INFORMATION FOR THE GARAGE |
| | DOOR.FIRE RATING REQUIREMENTS ARE NOT CLEAR DUE TO |
| | INSUFFICIENT INFORMATION, SEE ITEM 1. |
| | |
| | NEW COMMENT: |
| | |
| | 10.)THE ENGINEER STATES THAT PRODUCT APPROVALS ARE |
| | NOT REQUIRED AND STATES THAT THE DESIGN PRESSURE FOR |
| | THIS OPEING IS +-5 PSF.THIS OPENING, ALTHOUGH NOT ON |
| | AN EXTERIOR WALL, IS NEAR THE GARAGE ENTRY, A LARGE |
| | OPENING, AND IS SUBJECT TO WIND PRESSURES.PLEASE |
| | DECLARE WIND DESIGN CRITERIA FBC 1603.1.4.WIND TUNNEL |
| | TEST REPORT MAY BE AVAILABLE; APRIL PICCIRILLO, |
| | 561-805-6658. |