Plan Review Notes
Plan Review Notes For Permit 07040875
Permit Number 07040875
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-18 14:00:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL
 AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT
 ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 2ND REVIEW - NOT ADDRESSED.TENANT SEPARATION IS
 REQUIRED FBC708.1(5); REQUESTED INFORMATION WAS NOT
 PROVIDED.
  
 2.)THE INFORMATION IN REGARDS TO THE EXISTING
 BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT
 LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE
 INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE
 DESIGN PROFESSIONAL.
  
 2ND REVIEW - PROVIDE THE CODE SUMMARY AS REQUESTED;
 OCCUPANCY CLASSIFICATION FBC3, BUILDING TYPE FBC6,
 SPRINKLER INFORMATION.
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.
  
 NEW COMMENTS:
  
 5.)PLANS STATE "RELOCATE FIRE SPRINKLER HEAD".
 PROVIDE A PLAN.THE FIRE SPRINKLER PLAN IS REQUIRED AS
 A PART OF THIS PERMIT PACKAGE FS553.79(2),
 FBC*106.3.5.1.1(5).
  
 6.)ALL INFORMATION REQUIRED BY FAC61G15-23.002
 (ENGINEER) IS TO BE ON EACH SHEET.
  
 7.)TWO SETS OF ALL DOCUMENTS REQUIRED.ONLY ONE
 PRODUCT APPROVAL WAS SUBMITTED.
  
 8.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 9.)PROVIDE FIRE RATING INFORMATION FOR THE GARAGE
 DOOR.FIRE RATING REQUIREMENTS ARE NOT CLEAR DUE TO
 INSUFFICIENT INFORMATION, SEE ITEM 1.
  