Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop M
Sequence Number 4
Notes
Date Text
2007-10-10 11:09:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) FIRM LICENSE NUMBER IN THE TITLE BLOCK FOR A.J.O.
 ARCH. IS INCORRECT SEE RED LINE ON PLANS, PLEASE
 CORRECT PER FAC 61G1-16.004 TITLE BLOCK.
  
 2) PAGE M2.01 AIR BALANCE SCHEDULE HAS INCORRECT
 INFORMATION IN IT, BATH EXHAUST SHOWS 500 SHOULD SHOW
 550 (EF-1 50CFM'S AND TWO EF-2 AT 250 CFM'S EACH =550
 CFM'S). ALSO THE TOTALS FOR O/A, R/A, AND PRESSURE/CFM
 ARE INCORRECT, PLEASE CORRECT AND COMPLY WITH 2004 FBC
 13-409.1.ABC.3.6.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]