Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop E
Sequence Number 4
Notes
Date Text
2007-10-23 10:53:57***PROVISO/REVISION NEEDED ***
  
 1) NOTE: PLEASE SEE THE LIGHTING IN THE KITCHEN BACK
 HALLWAY AREA NEEDS TO MEET BOTH THE LIFE SAFETY ASPECT
 OF THE CODE IN NFPA-101 7.8/ALONG WITH FBC AND CHAPTER
 13 FOR LIGHTING CONTROLS.
 AS SHOWN ON PLANS WHEN THE SCHEDULED LIGHTING SYSTEM
 TURNS OFF THERE IS NO DEVICE OR LIGHTING PROVIDED FOR
 THE PATH TO THE OVER RIDE DEVICES.
 THERE IS ALSO NO *NIGHT-LIGHTS* SHOWN IN THESE SAME
 AREAS. THIS WAS GONE OVER IN MEETING AND AGREED THESE
 LIGHTING FIXTURES OR OCCUPANCY SENSORS WILL BE
 PROVIDED.
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 2) NOTE: REDLINED METHOD OF LIGHTING CALCULATIONS FROM
 METHOD *A* TO METHOD *C* AS GONE OVER IN MEETING.
  
 ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER
 REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  