Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop P
Sequence Number 3
Notes
Date Text
2007-10-03 14:10:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT
 NUMBERS TO REMAIN THE SAME.
 ******FROM PREVIOUS REVIEWS:
  
 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE
 FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN
 THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES
 NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE
 DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN
 REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE
 NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL
 SHEETS WITH ARCHITECTURAL TITLE BLOCK. ******RESPONSE
 NOTED, BUT THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. EITHER UPDATE THE DBPR WEBSITE OR THE TITLE
 BLOCKS PRIOR TO RESUBMITTING FOR REVIEW.
  
 2. OK
 3. OK
  
 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE
 SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET
 ROOMS)
  
 __FOR W/C'S:
 A. OK
 B. OK
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED
 ******RESPONSE NOTED BUT THE REQUIREMENT IS FOR THE
 FLUSH CONTROL TO BE ON THE WIDE SIDE OF THE W/C.
 DETAILS 1 & 9 SHOW THE FLUSH HANDLE ON THE WALL SIDE OF
 THE W/C. DETAIL 9 ALSO SHOWS THE W/C 17" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. 18" IS REQUIRED. (SEE
 FIGURE 11-28).
 E. OK
  
 __FOR URINALS:
 A. 11-4.18.2 OK
 B. 11-4.18.3 OK
 C. 11-4.18.4 OK
  
 __FOR LAVS:
 A. 11-4.19.2 OK
 B. 11-4.19.3 OK
 C. 11-4.19.4 OK
 D. 11-4.19.5 FAUCETS ****NOT ADDRESSED ******RESPONSE
 NOTED, BUT THE REQUIREMENT FOR THE LAV FAUCETS IS FOR
 THE OPERATING CONTROLS, NOT THE HEIGHT. LEVER TYPE,
 PUSH TYPE, ELECTRONICALLY CONTROLLED ETC. INDICATE
 FAUCET TYPE.
 E. 11-4.19.6 OK
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT
 FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE
 WITH ARCHITECT.
 ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND
 THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED.
  
 F. N/A
 G. N/A
 H. OK
 10. OK
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV
 BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE
 FLOOR FOR SERVICING & TESTING.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED
 AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN
 INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED.
 ******RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED
 AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN
 INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED.
 THE RPZV BACKFLOW IS STILL NOT INDICATED FOR THE
 SPACE.
  
 12. OK
 13. OK
 14. OK
  
 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS
 K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE
 TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED
 TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY
 DBPR.
 ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE
 THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT
 APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS
 OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN
 ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR
 EACH SET OF PLANS.
 ******RESPONSE NOTED, BUT THE SHEETS WITH THE DBPR
 SHEETS HAVE BEEN REMOVED. THE SHEETS WITH THE DBPR
 REVIEW STAMPS ARE REQUIRED IN EACH SET OF PLANS. ALSO
 AS INDICATED PREVIOUSLY, THE 2 PAGE "SPECIFICATION
 WORKSHEETS" HAVE NOT BEEN ATTACHED TO THE SHEETS WITH
 THE DBPR REVIEW STAMP. PLEASE SUBMIT SHEETS WITH THE
 DBPR REVIEW STAMP AND ATTACH THE TWO PAGE
 "SPECIFICATION WORKSHEETS" TO THE REVIEW SHEETS.
  
 16. OK
  
 ***********NEW COMMENTS**********
  
 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT
 CONNECT TO THE SANITARY DIRECTLY. SECTION 802.1.2.
 INDIRECT CONNECTION REQUIRED.
 ******RESPONSE NOTED, BUT A SAFE WASTE IS NOT AN
 INDIRECT WASTE. AN AIR GAP IS REQUIRED PER SECTION
 802.1.2. NO AIR GAP IS INDICATED.
  
 2B. OK
 3B. OK
 4B. OK
  
 **********NEW COMMENTS**********
  
 1C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT
 THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL
 BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER
 DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS.
 ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT.
  
 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE
 SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND
 A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END
 OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR
 THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY.A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved