| Date |
Text |
| 2007-10-03 14:10:18 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT |
| | NUMBERS TO REMAIN THE SAME. |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE |
| | FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN |
| | THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219, |
| | 481.2055. |
| | ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES |
| | NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE |
| | DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE |
| | TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN |
| | REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE |
| | NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL |
| | SHEETS WITH ARCHITECTURAL TITLE BLOCK. ******RESPONSE |
| | NOTED, BUT THE ADDRESS ON THE TITLE BLOCK DOES NOT |
| | REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR |
| | WEBSITE. EITHER UPDATE THE DBPR WEBSITE OR THE TITLE |
| | BLOCKS PRIOR TO RESUBMITTING FOR REVIEW. |
| | |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE |
| | SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET |
| | ROOMS) |
| | |
| | __FOR W/C'S: |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED |
| | ******RESPONSE NOTED BUT THE REQUIREMENT IS FOR THE |
| | FLUSH CONTROL TO BE ON THE WIDE SIDE OF THE W/C. |
| | DETAILS 1 & 9 SHOW THE FLUSH HANDLE ON THE WALL SIDE OF |
| | THE W/C. DETAIL 9 ALSO SHOWS THE W/C 17" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE. 18" IS REQUIRED. (SEE |
| | FIGURE 11-28). |
| | E. OK |
| | |
| | __FOR URINALS: |
| | A. 11-4.18.2 OK |
| | B. 11-4.18.3 OK |
| | C. 11-4.18.4 OK |
| | |
| | __FOR LAVS: |
| | A. 11-4.19.2 OK |
| | B. 11-4.19.3 OK |
| | C. 11-4.19.4 OK |
| | D. 11-4.19.5 FAUCETS ****NOT ADDRESSED ******RESPONSE |
| | NOTED, BUT THE REQUIREMENT FOR THE LAV FAUCETS IS FOR |
| | THE OPERATING CONTROLS, NOT THE HEIGHT. LEVER TYPE, |
| | PUSH TYPE, ELECTRONICALLY CONTROLLED ETC. INDICATE |
| | FAUCET TYPE. |
| | E. 11-4.19.6 OK |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO |
| | ISSUING THE GAS PERMIT: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT |
| | FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE |
| | WITH ARCHITECT. |
| | ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND |
| | THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED. |
| | |
| | F. N/A |
| | G. N/A |
| | H. OK |
| | 10. OK |
| | |
| | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE |
| | TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV |
| | BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE |
| | FLOOR FOR SERVICING & TESTING. |
| | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED |
| | AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN |
| | INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED. |
| | ******RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED |
| | AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN |
| | INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED. |
| | THE RPZV BACKFLOW IS STILL NOT INDICATED FOR THE |
| | SPACE. |
| | |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS |
| | K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE |
| | TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS |
| | REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED |
| | TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY |
| | DBPR. |
| | ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE |
| | THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT |
| | APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS |
| | OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN |
| | ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR |
| | EACH SET OF PLANS. |
| | ******RESPONSE NOTED, BUT THE SHEETS WITH THE DBPR |
| | SHEETS HAVE BEEN REMOVED. THE SHEETS WITH THE DBPR |
| | REVIEW STAMPS ARE REQUIRED IN EACH SET OF PLANS. ALSO |
| | AS INDICATED PREVIOUSLY, THE 2 PAGE "SPECIFICATION |
| | WORKSHEETS" HAVE NOT BEEN ATTACHED TO THE SHEETS WITH |
| | THE DBPR REVIEW STAMP. PLEASE SUBMIT SHEETS WITH THE |
| | DBPR REVIEW STAMP AND ATTACH THE TWO PAGE |
| | "SPECIFICATION WORKSHEETS" TO THE REVIEW SHEETS. |
| | |
| | 16. OK |
| | |
| | ***********NEW COMMENTS********** |
| | |
| | 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT |
| | CONNECT TO THE SANITARY DIRECTLY. SECTION 802.1.2. |
| | INDIRECT CONNECTION REQUIRED. |
| | ******RESPONSE NOTED, BUT A SAFE WASTE IS NOT AN |
| | INDIRECT WASTE. AN AIR GAP IS REQUIRED PER SECTION |
| | 802.1.2. NO AIR GAP IS INDICATED. |
| | |
| | 2B. OK |
| | 3B. OK |
| | 4B. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT |
| | THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL |
| | BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER |
| | DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS. |
| | ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT. |
| | |
| | 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE |
| | SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND |
| | A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END |
| | OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR |
| | THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY.A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |