| 2007-10-03 14:12:13 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO |
| | ISSUING THE GAS PERMIT: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT |
| | FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE |
| | WITH ARCHITECT. |
| | ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND |
| | THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED. |
| | |
| | F. N/A |
| | G. N/A |
| | H. OK |
| | 10. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT |
| | THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL |
| | BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER |
| | DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS. |
| | ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT. |
| | |
| | 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE |
| | SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND |
| | A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END |
| | OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR |
| | THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY.A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |