Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-27 18:48:48** DENIED**
  
 *** PLEASE SEE THE FOLLOWING COMMENTS BELOW.
 THERE HAVE BEEN SEVERAL ON PLANS WITH RESPECT TO
 LIGHTING CONTROLS AND NEW COMMENTS BELOW WHICH MAY NOT
 BE WORD FOR WORD THE SAME FROM PREVIOUS REVIEW STILL
 HAVE TO DO WITH CHAPTER 13 COMPLIANCE. AS SOME NEW
 METHODS/CHANGES IN CONTROLS HAVE BEEN REVISED THIS HAS
 CREATED A COUPLE OF NEW COMMENTS ON PLANS.
 ** PLEASE KNOW IF ALL OTHER REVIEWS PASS WITHOUT ANY
 COMMENTS, THE FOLLOWING MAY BE SET UP AS A PROVISO
 HOWEVER WOULD NEED TO BE REVISED WITH THE GIVEN TIME.
 THIS IS ONLY IF ALL OTHER TRADES ARE OK WITH PLANS AND
 PROJECT IS READY TO ISSUE FOR PERMIT.
 THE ELECTRICAL DESIGNER HAS BEEN CONTACTED.
  
 1) NOTE:PLEASE THE LOCATIONS OF LIGHTING CONTROLS
 NEED TO MEET 13-415.1.ABC.1.1. PLEASE SEE FOR EXAMPLE
 THE REAR DOOR ENTRANCE WHICH DOES NOT CONTAIN ANY OVER
 RIDE. THERE ARE SEVERAL LOCATIONS WHICH SHOW STANDARD
 3-WAY AND 4-WAY SWITCHES HOWEVER WITH OUT AN OVER RIDE
 DEVICE OF SYSTEM, THESE SWITCHES WOULD BE INOPERABLE.
 PLEASE SEE THE BATHROOMS WHICH INDICATE A STANDARD
 SWITCH FOR CONTROL OF LIGHTING ALONG WITH AN OCCUPANCY
 DEVICE. IF AN OCCUPANT LEAVES THE BATHROOM AND TURNS
 THIS SWITCH OFF THEN ANY REMAINING OCCUPANTS WOULD HAVE
 NO LIGHTING TO MAKE WAY TO THE SWITCH TO TURN LIGHTING
 BACK ON. THIS SCENARIO WAS GONE OVER WITH DESIGNER AND
 ADJUSTMENTS TO TYPE OF FIXTURES AND POSSIBLE NIGHTS
 WILL BE REVISED ON PLANS.
  
 2) NOTE: PLEASE SEE LIFE SAFETY CODE NFPA-101 7.8 AND
 7.9 WITH RESPECT TO EGRESS LIGHTING UNDER NORMAL AND
 EMERGENCY CONDITIONS. THE LIGHTING WHICH IS BEING
 CONTROLLED FROM SYSTEM WHEN BEING SHUT DOWN LEAVES
 SEVERAL AREAS IN TOTAL DARKNESS WITHOUT LENDING ANY
 LIGHTING FOR EGRESS TO AREAS FOR THE OVER RIDE
 CONTROLS. THIS IS ALSO TO COORDINATE WITH THE COMMENT
 #1 ABOVE WITH RESPECT TO RESTROOMS AND HALLWAY AREAS.
 THESE LOCATIONS WERESPECIFICALLY GONE OVER WITH THE
 DESIGNER AND ADJUSTMENTS ARE BEING MADE TO LIGHTING
 FIXTURE TYPES AND/OR CONTROLS.
  
 3) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS
 SHOWN. THIS REVISED RISER HAS COMPLETELY CHANGED FROM
 THE PREVIOUS REVIEWED PLANS. PLEASE SEE THE RISER SHOWS
 THIS SERVICE BEING TAPPED FROM A GUTTER WHICH IS TAPPED
 FROM THE LOAD SIDE GUTTER WHICH IS FED FROM METERS AND
 DISCONNECTS. THIS IS UNCLEAR HOW THIS GUTTER BEING
 SHOWN ON THE LOAD SIDE OF THE METERS AND TENANT MAINS
 FEED THIS SECONDARY GUTTER?
 AS SHOWN THIS DOES NOT SEEM POSSIBLE. THIS REVIEW WILL
 PLACE CALL TO LAND-LORD AND REQUEST A MEETING ON-SITE
 FBC 106.1.2/106.3.5.1.2, NEC 215.5, 230.70 ETC
 THIS IS COORDINATION OF PLANS AND RISER.
  
 4) NOTE: PLEASE SEE COMMENTS FROM FIRE REVIEWER AND
 POSSIBLE BUILDING AS THE FIRE ALARMS PLANS FP-1 SHEET
 WAS NOT SIGNED, DATED OR SEALED BY THE ENGINEER OF
 RECORD. THIS IS REQUIRED FOR BASE BUILDING PLANS EVEN
 THOUGH THIS IS UNDER A SEPARATE PERMIT. AS MENTIONED ON
 PREVIOUS REVIEW THIS IS STILL REQUIRED UNDER BASE BUILD
 OUT PLANS.
 PLEASE ALSO SEE THE FIRE SPRINKLER SHEET FP3.1 AS THIS
 SHEET ONLY CONTAINS A PRINTED SEAL OF SOME SORT ON
 TITLE BLOCKS. PLEASE SEE THE SEAL AS SHOWN WOULD NOT
 MEET FAC 61G15-23.002.
 PLEASE BE SURE THIS IS ADDRESS EVEN IF COMMENTS ARE NOT
 FROM OTHER REVIEWS. IF THESE ITEMS ARE THE ONLY ITEMS
 ON THESE SHEETS FOR COMPLIANCE, THEN THESE DESIGN
 PROFESSIONALS MAY COME INTO THIS OFFICE AND SIGN, DATE
 AND SEAL PLANS.
  
 5) NOTE: PLEASE DO NOT ATTACH PRODUCT APPROVALS AND
 SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
 THESE HAVE BEEN REMOVED BY THIS REVIEWER ON BOTH SETS.
 THESE DOCUMENTS SHOULD BE PLACED INTO TWO SEPARATE
 PACKAGES.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved