| Date |
Text |
| 2007-09-27 18:48:48 | ** DENIED** |
| | |
| | *** PLEASE SEE THE FOLLOWING COMMENTS BELOW. |
| | THERE HAVE BEEN SEVERAL ON PLANS WITH RESPECT TO |
| | LIGHTING CONTROLS AND NEW COMMENTS BELOW WHICH MAY NOT |
| | BE WORD FOR WORD THE SAME FROM PREVIOUS REVIEW STILL |
| | HAVE TO DO WITH CHAPTER 13 COMPLIANCE. AS SOME NEW |
| | METHODS/CHANGES IN CONTROLS HAVE BEEN REVISED THIS HAS |
| | CREATED A COUPLE OF NEW COMMENTS ON PLANS. |
| | ** PLEASE KNOW IF ALL OTHER REVIEWS PASS WITHOUT ANY |
| | COMMENTS, THE FOLLOWING MAY BE SET UP AS A PROVISO |
| | HOWEVER WOULD NEED TO BE REVISED WITH THE GIVEN TIME. |
| | THIS IS ONLY IF ALL OTHER TRADES ARE OK WITH PLANS AND |
| | PROJECT IS READY TO ISSUE FOR PERMIT. |
| | THE ELECTRICAL DESIGNER HAS BEEN CONTACTED. |
| | |
| | 1) NOTE:PLEASE THE LOCATIONS OF LIGHTING CONTROLS |
| | NEED TO MEET 13-415.1.ABC.1.1. PLEASE SEE FOR EXAMPLE |
| | THE REAR DOOR ENTRANCE WHICH DOES NOT CONTAIN ANY OVER |
| | RIDE. THERE ARE SEVERAL LOCATIONS WHICH SHOW STANDARD |
| | 3-WAY AND 4-WAY SWITCHES HOWEVER WITH OUT AN OVER RIDE |
| | DEVICE OF SYSTEM, THESE SWITCHES WOULD BE INOPERABLE. |
| | PLEASE SEE THE BATHROOMS WHICH INDICATE A STANDARD |
| | SWITCH FOR CONTROL OF LIGHTING ALONG WITH AN OCCUPANCY |
| | DEVICE. IF AN OCCUPANT LEAVES THE BATHROOM AND TURNS |
| | THIS SWITCH OFF THEN ANY REMAINING OCCUPANTS WOULD HAVE |
| | NO LIGHTING TO MAKE WAY TO THE SWITCH TO TURN LIGHTING |
| | BACK ON. THIS SCENARIO WAS GONE OVER WITH DESIGNER AND |
| | ADJUSTMENTS TO TYPE OF FIXTURES AND POSSIBLE NIGHTS |
| | WILL BE REVISED ON PLANS. |
| | |
| | 2) NOTE: PLEASE SEE LIFE SAFETY CODE NFPA-101 7.8 AND |
| | 7.9 WITH RESPECT TO EGRESS LIGHTING UNDER NORMAL AND |
| | EMERGENCY CONDITIONS. THE LIGHTING WHICH IS BEING |
| | CONTROLLED FROM SYSTEM WHEN BEING SHUT DOWN LEAVES |
| | SEVERAL AREAS IN TOTAL DARKNESS WITHOUT LENDING ANY |
| | LIGHTING FOR EGRESS TO AREAS FOR THE OVER RIDE |
| | CONTROLS. THIS IS ALSO TO COORDINATE WITH THE COMMENT |
| | #1 ABOVE WITH RESPECT TO RESTROOMS AND HALLWAY AREAS. |
| | THESE LOCATIONS WERESPECIFICALLY GONE OVER WITH THE |
| | DESIGNER AND ADJUSTMENTS ARE BEING MADE TO LIGHTING |
| | FIXTURE TYPES AND/OR CONTROLS. |
| | |
| | 3) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS |
| | SHOWN. THIS REVISED RISER HAS COMPLETELY CHANGED FROM |
| | THE PREVIOUS REVIEWED PLANS. PLEASE SEE THE RISER SHOWS |
| | THIS SERVICE BEING TAPPED FROM A GUTTER WHICH IS TAPPED |
| | FROM THE LOAD SIDE GUTTER WHICH IS FED FROM METERS AND |
| | DISCONNECTS. THIS IS UNCLEAR HOW THIS GUTTER BEING |
| | SHOWN ON THE LOAD SIDE OF THE METERS AND TENANT MAINS |
| | FEED THIS SECONDARY GUTTER? |
| | AS SHOWN THIS DOES NOT SEEM POSSIBLE. THIS REVIEW WILL |
| | PLACE CALL TO LAND-LORD AND REQUEST A MEETING ON-SITE |
| | FBC 106.1.2/106.3.5.1.2, NEC 215.5, 230.70 ETC |
| | THIS IS COORDINATION OF PLANS AND RISER. |
| | |
| | 4) NOTE: PLEASE SEE COMMENTS FROM FIRE REVIEWER AND |
| | POSSIBLE BUILDING AS THE FIRE ALARMS PLANS FP-1 SHEET |
| | WAS NOT SIGNED, DATED OR SEALED BY THE ENGINEER OF |
| | RECORD. THIS IS REQUIRED FOR BASE BUILDING PLANS EVEN |
| | THOUGH THIS IS UNDER A SEPARATE PERMIT. AS MENTIONED ON |
| | PREVIOUS REVIEW THIS IS STILL REQUIRED UNDER BASE BUILD |
| | OUT PLANS. |
| | PLEASE ALSO SEE THE FIRE SPRINKLER SHEET FP3.1 AS THIS |
| | SHEET ONLY CONTAINS A PRINTED SEAL OF SOME SORT ON |
| | TITLE BLOCKS. PLEASE SEE THE SEAL AS SHOWN WOULD NOT |
| | MEET FAC 61G15-23.002. |
| | PLEASE BE SURE THIS IS ADDRESS EVEN IF COMMENTS ARE NOT |
| | FROM OTHER REVIEWS. IF THESE ITEMS ARE THE ONLY ITEMS |
| | ON THESE SHEETS FOR COMPLIANCE, THEN THESE DESIGN |
| | PROFESSIONALS MAY COME INTO THIS OFFICE AND SIGN, DATE |
| | AND SEAL PLANS. |
| | |
| | 5) NOTE: PLEASE DO NOT ATTACH PRODUCT APPROVALS AND |
| | SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS. |
| | THESE HAVE BEEN REMOVED BY THIS REVIEWER ON BOTH SETS. |
| | THESE DOCUMENTS SHOULD BE PLACED INTO TWO SEPARATE |
| | PACKAGES. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |