Plan Review Notes
Plan Review Notes For Permit 07040835
Permit Number 07040835
Review Stop B
Sequence Number 3
Notes
Date Text
2007-10-01 13:34:55TAVERNA OPA 2ND REVIEW
 700 S. ROSEMARY
 BUILDING PLAN REVIEW
 PERMIT: 07040835
 ADD: 700 S ROSEMARY # 232
 CONT: L. DAVIS CONSTRUCTION
 TEL: (561)718-8161
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW ? BUILDING8-25-07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUNDWILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-7) COMPLIED.
  
 8) RED LINE ACI-318-02 UPDATE
 ACI 531-79 NOT EVEN LISTED
 ACI 530.1-05 THERE IS THIS NUMBER FOR
 MASONRY REQUIREMENTS
 9-19) COMPLIED.
  
 20) COMPLIED.
  
 21-23) COMPLIED.
  
 24) CHANGE IN OCCUPANCY,BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 25) NEW COMMENT, SHEET S3 DETAIL # 1, SEE NOTES FOR
 STRUCTURAL MULLIONS,NOTES 8,9 & 10 INDICATE THE
 MULLIONS ARE VERTICAL WHEN THEY ARE HORIZONTAL.
  
 26) NEW COMMENT, CHANGE OF CONTRACTOR PLEASE NOTE THE
 PERMIT APPLICATION SUBMITTED INDICATES 700 S ROSEMARY
 SUITE 100, WHERE ASTHE RESUB SHEET AND ORIGINAL
 CONTRACTOR PERMIT APPLICATION INDICATES SUITE # 232
 AAAS WELL AS THE PLANS. PLEASE CORRECT.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  